Table 3 North America/Japan Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
24 A
24 A
12 kW
Output Load
208V 3P Delta
208V 3P Delta
208V 3P Wye
Input Voltage
NEMA L15-30P
NEMA L15-30P
IEC309 560P9
Input Connector
N/A
N/A
208V 3P Delta
Output Voltage
6 x C19
6 x C19
2 x NEMA L15-30R
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 4 International Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
32 A
32 A
4500 W
Output Load
200 – 240 V
200 – 240 V
220 – 240 V
Input Voltage
IEC309 332P6
IEC309 332P6
IEC309 332P6
Input Connector
(32 A)
(32 A)
(32 A)
N/A
N/A
220 – 240 V
Output Voltage
4x C19
6 x C19
1 x IEC309 332R6
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 5 International Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
16 A/phase
16 A/phase
12 kW
Output Load
380-415V 3P Wye
380-415V 3P Wye
380-415V 3P Wye
Input Voltage
IEC309 516P6
IEC309 516P6
IEC309 532P6
Input Connector
(32 A)
(32 A)
(32 A)
AC Input Power for Modular Cabinets
59
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...