Technical Specifications
This appendix contains technical specification information about your system.
System Specifications and Features
The table following lists the physical and electrical specifications of the HPE Apollo 480 Cluster.
System Features
Specification
Cabinet height
85.6 in. (217.4 cm)
Cabinet width
24 in. (61 cm)
Cabinet depth
48 in. (121.9)
Weight (full) maximum
Approximately 2,579 lbs. Shipping weight will be
greater.
Phase required
Four three-phase PDUs per rack
Voltage and CPS range
North America - nominal voltage is 208V at 24A per
phase (50/60hz for 3W+PE)
Europe - nominal voltage is 415V at 30A per phase
(50/60hz for 3W+ N+PE)
Power cables
Four three-phase pluggable cords per rack
Power supplies
Two per compute enclosure (2000W minimum per
power supply)
Cooling
Compute enclosure fans (40mm x4 per enclosure)
Hard drive bays
Up to 2 per node, up to 48 in front bay
PCIe slots
Optional low-profile (x16) PCI-Express slots on
HPC compute nodes
Environmental Specifications
The table following lists the environmental specifications of the Apollo 480 system.
Feature
Specification
Temperature tolerance (operating)
+5°C (45°F) to +35°C (95°F) (up to 1500 m / 5000
ft.)
Temperature tolerance (nonoperating)
-40°C (-41°F) to +60°C (140°F)
Relative humidity
20% to 80% operating (no condensation)
8% to 80% nonoperating (no condensation)
Cooling requirement
Ambient air cooling
Maximum altitude
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) nonoperating
Acoustical noise level (sound pressure)
Less than 90 dBA maximum
14