76
Programming the HP E1415 for PID Control
positions they are currently in. The calibration becomes invalid if you move
these SCPs to different SCP locations.
How to Use *CAL?
When you turn power on to the HP E1415 after you have first installed your
SCPs (or after you have moved SCPs), the module will use approximate
values for calibration constants. This means that input and output channels
will function although the values will not be very accurate relative to the
HP E1415’s specified capability. At this point, make sure the module is
firmly anchored to the mainframe (front panel screws are tight), and let it
warm up for a full hour. After it has warmed up, execute *CAL?.
What *CAL? Does
The *CAL? command causes the module to calibrate A/D offset and gain,
and all channel offsets. This may take many minutes to complete. The actual
time it will take your HP E1415 to complete *CAL? depends on the mix of
SCPs installed. *CAL? performs literally hundreds of measurements of the
internal calibration sources for each channel and must allow 17 time
constants of settling wait each time a filtered channel’s calibration source
changes value. The *CAL? procedure is internally very sophisticated and
results in an extremely well calibrated module.
When *CAL? finishes, it returns a +0 value to indicate success. The
generated calibration constants are now in volatile memory as they always
are when ready to use. If the configuration just calibrated is to be fairly
long-term, you should now execute the CAL:STORE
ADC command to
store these constants in non-volatile memory. That way the module can
restore calibration constants for this configuration in case of a power failure.
After power returns, and after the module warms up, these constants will be
relatively accurate.
Re-Execute
*CAL? When:
•
When you change the channel gain and/or filter cut-off frequency on
programmable SCPs (using INPut:GAIN, or INPut:FILTer ... )
•
When you re-configure SCPs to different locations. This is true even if
you replace an SCP with an identical model SCP because the
calibration constants are specific to each SCP channel’s individual
performance.
•
When the ambient temperature within the mainframe changes
significantly. Temperature changes affect accuracy much more than
long-term component drift. See temperature coefficients in Appendix
A page 305 "Specifications".
NOTE
To save time when performing channel calibration on multiple HP E1415s
in the same mainframe, use the CAL:SETup and CAL:SETup? commands
(See “CALibration:SETup” on page 188. for details).
Содержание VXI 75000 C Series
Страница 2: ......
Страница 16: ...16 ...
Страница 18: ......
Страница 30: ...30 Getting Started Chapter 1 Notes ...
Страница 32: ...32 Field Wiring Chapter 2 Figure 2 1 Channel Numbers at SCP Positions ...
Страница 44: ...44 Field Wiring Chapter 2 Figure 2 11 HP E1415 Terminal Module ...
Страница 54: ...54 Field Wiring Chapter 2 Notes ...
Страница 61: ...Programming the HP E1415 for PID Control 61 Chapter 3 Programming Overview Diagram ...
Страница 124: ...124 Creating and Running Custom Algorithms Chapter 4 Figure 4 2 Algorithm Operating Sequence Diagram ...
Страница 136: ...136 Creating and Running Custom Algorithms Chapter 4 Notes ...
Страница 152: ...152 Algorithm Language Reference Chapter 5 Notes ...
Страница 304: ...304 HP E1415 Command Reference Chapter 6 Command Quick Reference Notes ...
Страница 308: ...308 Specifications Appendix A Thermocouple Type E 200 800C SCPs HP E1501 02 03 ...
Страница 309: ...Specifications 309 Appendix A Thermocouple Type E 200 800C SCPs HP E1508 09 ...
Страница 310: ...310 Specifications Appendix A Thermocouple Type E 0 800C SCPs HP E1501 02 03 ...
Страница 311: ...Specifications 311 Appendix A Thermocouple Type E 0 800C SCPs HP E1509 09 ...
Страница 312: ...312 Specifications Appendix A Thermocouple Type E Extended SCPs HP E1501 02 03 ...
Страница 313: ...Specifications 313 Appendix A Thermocouple Type E Extended SCPs HP E1508 09 ...
Страница 314: ...314 Specifications Appendix A Thermocouple Type J SCPs HP E1501 02 03 ...
Страница 315: ...Specifications 315 Appendix A Thermocouple Type J SCPs HP E1508 09 ...
Страница 316: ...316 Specifications Appendix A Thermocouple Type K SCPs HP E1501 02 03 ...
Страница 317: ...Specifications 317 Appendix A Thermocouple Type R SCPs HP E1501 02 03 ...
Страница 318: ...318 Specifications Appendix A Thermocouple Type R SCPs HP E1508 09 ...
Страница 319: ...Specifications 319 Appendix A Thermocouple Type S SCPs HP E1501 02 03 ...
Страница 320: ...320 Specifications Appendix A Thermocouple Type S SCPs HP E1508 09 ...
Страница 321: ...Specifications 321 Appendix A Thermocouple Type T SCPs HP E1501 02 03 ...
Страница 322: ...322 Specifications Appendix A Thermocouple Type T SCPs HP E1508 09 ...
Страница 323: ...Specifications 323 Appendix A 5K Thermistor Reference SCPs HP E1501 02 03 ...
Страница 324: ...324 Specifications Appendix A 5K Thermistor Reference SCPs HP E1508 09 ...
Страница 325: ...Specifications 325 Appendix A RTD Reference SCPs HP E1501 02 03 ...
Страница 326: ...326 Specifications Appendix A RTD SCPs HP E1501 02 03 ...
Страница 327: ...Specifications 327 Appendix A RTD SCPs HP E1508 09 ...
Страница 328: ...328 Specifications Appendix A 2250 Thermistor SCPs HP E1501 02 03 ...
Страница 329: ...Specifications 329 Appendix A 2250 Thermistor SCPs HP E1508 09 ...
Страница 330: ...330 Specifications Appendix A 5K Thermistor SCPs HP E1501 02 03 ...
Страница 331: ...Specifications 331 Appendix A 5K Thermistor SCPs HP E1508 09 ...
Страница 332: ...332 Specifications Appendix A 10K Thermistor SCPs HP E1501 02 03 ...
Страница 333: ...Specifications 333 Appendix A 10K Thermistor SCPs HP E1508 09 ...
Страница 334: ...334 Specifications Appendix A Notes ...
Страница 346: ...346 Glossary Appendix C Notes ...
Страница 388: ...388 Generating User Defined Functions Appendix F Notes ...
Страница 438: ...438 Index Writing the algorithm 129 values to CVT elements 120 values to the FIFO 121 Z ZERO CALibration ZERO 194 ...