Selecting the UPS Voltage Configuration
To select the UPS voltage:
1. Power down the UPS by pressing the On/Standby button (1).
1
Figure 3-2: On/Standby button
2. Position the DIP switches according to the desired voltage configuration as identified on
the rear panel of the UPS unit. The switch position for each configuration is described in
Table 3-1 and shown in Figure 3-3 through Figure 3-7.
Table 3-1: T700 Voltage Configuration DIP Switch Settings
Low-Voltage North America Model
Output Voltage
Input Voltage Range
DIP Switch 2
DIP Switch 1
110 V
99 V to 116 V
On or Off
On
120 V*
108 V to 127 V*
On or Off
Off
High-Voltage International Model
Output Voltage
Input Voltage Range
DIP Switch 2
DIP Switch 1
220 V
198 V to 233 V
Off
On
230 V*
207 V to 243 V*
On or Off
Off
240 V
216 V to 254 V
On
On
* Indicates default setting. DIP switch settings indicating
On
or
Off
specify that the DIP switch can
be placed in either the On or Off position. The
X
on the UPS rear panel of each unit also indicates
that the DIP switch can be positioned On or Off.
IMPORTANT:
The UPS T700 JPN model does not include the rear panel voltage configuration
DIP switch feature, since this model cannot be altered from the 100 V configuration setting.