Diagnostics
81
Did CTP card replacement solve the problem?
NO
YES
↓
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
7
An SBAR assembly failed POSTs (indicated by a 03 FRU code) and must be
removed and replaced (“
■
This procedure is concurrent and can be performed while director power is on.
■
Perform the data collection procedure as part of FRU removal and
replacement.
Did SBAR assembly replacement solve the problem?
NO
YES
↓
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
8
A fan module failed POSTs (indicated by a 05 FRU code) and must be removed
and replaced (“
■
This procedure is concurrent and can be performed while director power is on.
■
Perform the data collection procedure as part of FRU removal and
replacement.
Note:
Do not remove a fan module unless the replacement module is available.
Operation of the director with only one fan module for an extended period may cause
one or more thermal sensors to post event codes.
Did fan module replacement solve the problem?
NO
YES
↓
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
Содержание StorageWorks 2/140 - Director Switch
Страница 18: ...About this Guide 18 Director 2 140 Service Manual ...
Страница 160: ...Diagnostics 160 Director 2 140 Service Manual ...
Страница 224: ...FRU Removal and Replacement 224 Director 2 140 Service Manual Figure 72 ESD grounding points 1 ...
Страница 262: ...FRU Removal and Replacement 262 Director 2 140 Service Manual ...
Страница 270: ...Illustrated Parts Breakdown 270 Director 2 140 Service Manual ...
Страница 318: ...Information and Error Messages 318 Error Messages ...
Страница 388: ...Event Code Tables 388 Director 2 140 Service Manual ...