Repair Information
190
2. Open the HAFM application. The View All - HAFM 8 main window displays.
a.
Double-click the icon representing the director for which the channel
wrap test will be configured. The Hardware View for the selected
director displays.
b. At the Hardware View, verify the location of the port to be configured
for the channel wrap test. When the mouse pointer is passed over a
graphical UPM card on the front view of the director, the card highlights
with a blue border and a pop-up displays with the following information:
— Port card type (UPM).
— Chassis slot number (0 through 35, slot 32 is for internal use only).
— The four consecutive port numbers on the selected card. Valid port
numbers are in the range of (0-127 and 132-143 inclusive).
c.
Double-click the UPM card with the port to be configured. The Port
Card View for the selected card displays.
d. Right-click the port to be configured, then choose Channel Wrap from
the menu. The Channel Wrap On for Port n (where n is the port
number) window displays.
e.
Click OK to enable channel wrapping for the port.
3. Perform the Fibre Channel link test at the FICON host attached to the
configured port. For test instructions, refer to the service documentation
delivered with the FICON system.
Swapping Ports (FICON)
Use the port swap procedure to swap a device connection and logical port address
from a failed Fibre Channel port to an operational port. Because both ports are
blocked during the procedure, director communication with the attached device is
momentarily disrupted.
To perform the port swap procedure for a pair of director ports:
1. Notify the customer a port swap procedure will be performed and a fiber optic
cable or cables will be disconnected. Ensure the customer’s system
administrator quiesces Fibre Channel frame traffic through the ports and sets
attached devices offline.
2. Open the HAFM application. The View All - HAFM 8 main window displays.
3. Double-click the icon representing the director for which the loopback test
will be performed. The Hardware View for the selected director displays.
Содержание StorageWorks 2/140 - Director Switch
Страница 18: ...About this Guide 18 Director 2 140 Service Manual ...
Страница 160: ...Diagnostics 160 Director 2 140 Service Manual ...
Страница 224: ...FRU Removal and Replacement 224 Director 2 140 Service Manual Figure 72 ESD grounding points 1 ...
Страница 262: ...FRU Removal and Replacement 262 Director 2 140 Service Manual ...
Страница 270: ...Illustrated Parts Breakdown 270 Director 2 140 Service Manual ...
Страница 318: ...Information and Error Messages 318 Error Messages ...
Страница 388: ...Event Code Tables 388 Director 2 140 Service Manual ...