Diagnostics
122
Did one of the listed messages display in the Link Incident Log?
YES
NO
↓
The director is operational. Exit MAP.
14
A Fibre Channel port or UPM card (all ports) failed an internal or external
loopback test.
1. Reset each port that failed the loopback test.
a.
At the Hardware View, right-click the port. A menu displays.
b. Choose Reset Port. A
Reset Port n
message box displays, where
n
is the port number.
c.
Click OK. The port resets.
2. Perform an external loopback test for all ports that were reset.
Did resetting ports solve the problem?
NO
YES
↓
The director is operational. Exit MAP.
15
An electronic circuit breaker on the UPM card may have tripped. To reset the
circuit breaker, partially remove and reseat the UPM card for which external
loopback tests failed (“
1. Unseat and disconnect the UPM card from the backplane. Unseat the card
only, do not remove it from the director chassis.
2. Reseat the UPM card in the backplane.
3. Perform an external loopback test on the UPM card.
Did reseating the UPM card solve the problem?
NO
YES
↓
The director is operational. Exit MAP.
.
Содержание StorageWorks 2/140 - Director Switch
Страница 18: ...About this Guide 18 Director 2 140 Service Manual ...
Страница 160: ...Diagnostics 160 Director 2 140 Service Manual ...
Страница 224: ...FRU Removal and Replacement 224 Director 2 140 Service Manual Figure 72 ESD grounding points 1 ...
Страница 262: ...FRU Removal and Replacement 262 Director 2 140 Service Manual ...
Страница 270: ...Illustrated Parts Breakdown 270 Director 2 140 Service Manual ...
Страница 318: ...Information and Error Messages 318 Error Messages ...
Страница 388: ...Event Code Tables 388 Director 2 140 Service Manual ...