Removal and replacement procedures 37
To install the HDD cage:
1.
Position the HDD cage in the tray and install it as shown in below figure.
2.
Fasten the two thumbscrews.
3.
Fasten the screws in the upper corner.
Figure 9
Installing the HDD cage
CAUTION:
The HP ProLiant SL390s G7 4U Half-width Server supports disk drive hot-swapping. To
avoid hand contact with an electrical hazard, do not remove more than one drive carrier a time.
To install an SFF hard drive:
1.
Push the SFF hard drive into the HDD cage until it stops.
2.
Press the SFF hard drive cam latch inward until it clicks.
Figure 10
Installing a hot-plug hard disk drives or SSDs
IMPORTANT:
Do not discard the hard drive blank. If the drive is removed in the future, you must
reinstall the hard drive blank to maintain proper system airflow.