Table 6 International Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
International
16 A/phase
16 A/phase
12 kW
Output Load
380-415V 3P Wye
380-415V 3P Wye
380-415V 3P Wye
Input Voltage
IEC309 516P6
IEC309 516P6
IEC309 532P6
Input Connector
N/A
N/A
400V 3P Wye
Output Voltage
6 x C19 (20 A)
6 x C19
2 x IEC309 309 516C6
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
Enclosure AC Input for NS7 Systems
Enclosures (IP CLIM, SAS disk enclosure, and so forth) require:
Value
Specification
200/208/220/230/240 V AC RMS
Nominal input voltage
180-264 V AC
Voltage range
50 or 60 Hz
Nominal line frequency
47-53 Hz or 57-63 Hz
Frequency ranges
1
Number of phases
Single-phase c7000 enclosures require:
Value
Specification
200-240 VAC
Voltage range
50 or 60 Hz
Nominal line frequency
47-53 Hz or 57-63 Hz
Frequency ranges
1
Number of phases
AC Input Power for NS7 Racks
47
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...