Table 4 North America/Japan Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
North America/Japan
24 A
24 A
12 kW
Output Load
208V 3P Delta
208V 3P Delta
208V 3P Wye
Input Voltage
NEMA L15-30P
NEMA L15-30P
IEC309 560P9
Input Connector
N/A
N/A
208V 3P Delta
Output Voltage
6 x C19
6 x C19
2 x NEMA L15-30R
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 5 International Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
International
32 A
32 A
4500 W
Output Load
200 – 240 V
200 – 240 V
220 – 240 V
Input Voltage
IEC309 332P6
IEC309 332P6
IEC309 332P6
Input Connector
N/A
N/A
220 – 240 V
Output Voltage
4x C19
6 x C19
1 x IEC309 332R6
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
46
NS7 System Installation Specifications
Содержание Integrity NonStop X NS7
Страница 8: ...Figure 1 Example NS7 System Configurations 42U and 36U 8 HPE Integrity NonStop X NS7 Systems ...
Страница 39: ...Figure 14 Example of Bottom AC Power Feed in a Rack Without UPS AC Power Feeds in the Rack 39 ...
Страница 40: ...Figure 15 Example of Top AC Power Feed in a Rack Without UPS 40 NS7 System Installation Specifications ...
Страница 41: ...Figure 16 Example of Top AC Power Feed in a Rack With Single Phase UPS AC Power Feeds in the Rack 41 ...
Страница 43: ...Figure 18 Example of Top AC Power Feed in a Rack With Three Phase UPS AC Power Feeds in the Rack 43 ...
Страница 62: ...62 HPE Integrity NonStop X NS7 CG X2 System ...