Rack Stability
Rack stabilizers are required when you have less than four racks bayed together.
NOTE:
Rack stability is of special concern when equipment is routinely installed, removed, or
accessed within the rack. Stability is addressed through the use of leveling feet, baying kits, fixed
stabilizers, and/or ballast. Use baying kits to bay Intelligent racks to Intelligent racks of the same
height. In all cases, a rack cannot be bayed with another rack of a different height.
For information about best practices for racks or grounding the racks using a rack ground bonding
kit, your service provider can refer to:
•
HP Rack Options Installation Guide
•
http://www.hpe.com/support/Intelligent_Series_Rack_Manuals
Environmental Specifications
Heat Dissipation Specifications and Worksheet
Total (BTU/hour)
Unit Heat
(BTU/hour)
Maximum
Unit Heat
(BTU/hour) Typical
Number Installed
Enclosure Type
1212
924
16 GB CPU
1240
938
32 GB CPU
1268
952
48 GB CPU
1112
894
VIO enclosure
768
461
G6 Storage CLIM
682
444
G6 IP or Telco CLIM
699
419
Gen8 Storage CLIM
692
399
Gen8 Networking
CLIM, 5 copper ports
(IP or Telco)
716
419
Gen8 Networking
CLIM, 3 copper
ports/2 optical ports
(IP or Telco)
614
443
Gen9 Networking
CLIM, 5 copper ports
(IP or Telco)
631
461
Gen9 Networking
CLIM, 3 copper
ports/2 optical ports
(IP or Telco)
427
256
D2700 SAS disk
enclosure (no disks)
427
256
D3700 SAS disk
enclosure (no disks)
30
17
SAS 2.5 in. 10k rpm
disk drive
24
14
SAS 2.5 in. 15k rpm
disk drive
Rack Stability
53
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...