Table 3 International Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
32 A
32 A
4500 W
Output Load
200 – 240 V
200 – 240 V
220 – 240 V
Input Voltage
IEC309 332P6
IEC309 332P6
IEC309 332P6
Input Connector
(32 A)
(32 A)
(32 A)
N/A
N/A
220 – 240 V
Output Voltage
4x C19
6 x C19
1 x IEC309 332R6
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes
Table 4 International Three-Phase Power Specifications
Modular PDU 3-phase
iPDU 3-phase
R12000 3-phase UPS
16 A/phase
16 A/phase
12 kW
Output Load
380-415V 3P Wye
380-415V 3P Wye
380-415V 3P Wye
Input Voltage
IEC309 516P6
IEC309 516P6
IEC309 532P6
Input Connector
(32 A)
(32 A)
(32 A)
N/A
N/A
400V 3P Wye
Output Voltage
6 x C19 (20 A)
6 x C19
2 x IEC309 309 516C6
Output Connectors
(42 x C13)
(20 x C13)
UPS outputs are connected to the compatible PDU inputs.
Notes
46
System Installation Specifications for NS2300 Systems
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...