HSG80 Array Controller V8.7 Command Line Interface Reference Guide
2–115
SET controller
TERMINAL_PARITY=ODD
TERMINAL_PARITY=EVEN
NOTERMINAL_PARITY (default)
Specifies the parity with which data is transmitted and received. When changed,
the new setting for this switch takes effect immediately.
TERMINAL_SPEED=baud-rate
TERMINAL_SPEED=9600 (default)
Sets the terminal transmission and reception speed (baud rate) to 4800, 9600
(default), or 19200 baud. When changed, the new value entered for this switch
takes effect immediately.
TIME=dd–mmm–yyyy:hh:mm:ss
Sets the date and time using a 24-hour clock. The time is set on both controllers in
a dual-redundant configuration. When changed, the new value entered for this
switch takes effect immediately.
UPS=NODE_ONLY
UPS=DATACENTER_WIDE
NOUPS
Specifies whether the controller should perform regular battery condition checks.
Setting the UPS/NOUPS switch for either controller sets the switch for both
controllers. Both controllers must be restarted in order for the new setting to take
effect.
•
Specify UPS=NODE_ONLY if your storage subsystem power is supplied by a
separate uninterruptible power supply (UPS) directly connected to a PVA
module. If NODE_ONLY is specified the controller continues to check the
condition of the cache batteries.
CAUTION: Setting UPS=NODE_ONLY or UPS=DATACENTER_WIDE without having
a UPS or similar backup system in place may result in data loss if power is interrupted.
•
Specify UPS=DATACENTER_WIDE if the whole room or building (not just
the subsystem) is supported by a UPS. If DATACENTER_WIDE is specified,
the controller does not check the condition of the cache batteries and ignores
the battery’s state. This causes RAIDsets and mirrorsets to always be
available, regardless of the condition of the cache batteries.
•
Specify NOUPS to instruct the controller to perform regular cache battery
checks and evaluate the condition of the cache batteries.