Specifications 98
Power supply output
Rated steady-state power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power (W)
800 W at -40 VDC to -72 VDC
WARNING:
To reduce the risk of electric shock or energy hazards:
•
This equipment must be installed by trained service personnel, as defined by the NEC and
IEC 60950-1, Second Edition, the standard for Safety of Information Technology
Equipment.
•
Connect the equipment to a reliably grounded Secondary circuit source. A Secondary
circuit has no direct connection to a Primary circuit and derives its power from a
transformer, converter, or equivalent isolation device.
•
The branch circuit overcurrent protection must be rated 27 A.
CAUTION:
This equipment is designed to permit the connection of the earthed conductor of
the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
•
This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC
supply system earthing electrode conductor is connected.
•
This equipment must be located in the same immediate area (such as adjacent cabinets) as
any other equipment that has a connection between the earthed conductor of the same DC
supply circuit and the earthing conductor, and also the point of earthing of the DC system.
The DC system must be earthed elsewhere.
•
The DC supply source is to be located within the same premises as the equipment.
•
Switching or disconnecting devices must not be in the earthed circuit conductor between
the DC source and the point of connection of the earthing electrode conductor.
HPE 1400W Flex Slot Platinum Plus Hot-plug Power Supply
Specification
Value
Input requirements
Rated input voltage
200 to 240 VAC
240 VDC for China only
Rated input frequency
50 Hz to 60 Hz
Not applicable to 240 VDC
Rated input current
8.0 A at 200 VAC
6.7 A at 240 VAC
6.7 A at 240 VDC for China only
Maximum rated input power
1600 W at 200 VAC
1600 W at 240 VAC
1600 W at 240 VDC for China
only
BTUs per hour
5459 at 200 VAC
5459 at 240 VAC
5459 at 240 VDC for China only
Power supply output
Rated steady-state power
1400 W at 200 VAC to 240 VAC
input
1400 W at 240 VDC input for
China only
Maximum peak power
1400 W at 200 VAC to 240 VAC
input
1400 W at 240 VDC input for