Installation

Testing the system

It is assumed that installers are familiar with installing cables and fixing the 

Turn the keyswitch to TEST MODE. The sounder will give a low pitch bleep 

various components etc.. The system is battery powered and presents no 

every 5 secs. Insert the black test key in the underside of the call point to 

electrical  risk  to  either  installers  or  users.  Callpoint/Sounder  units  are 

displace the glass. Only the control sounder will sound. Remove the test key. 

generally fitted at a height of 1.2m AFL. Remove the front cover and glass 

While still in TEST MODE visit each call point in turn. Inserting the black test 

and separate the back box. Pre-drill the back boxes if necessary to take the 

key  sounds  only  the  sounder  of  the  call  point  being  tested.  When  all  call 

interconnection cable. Fit the back boxes to the wall and introduce the 

points have been tested switch the control to the RESTART position.

cable. Strip the sheathing and cores as necessary.

Fault Finding

Start connecting at the remote End of Line unit and work back towards the 

Fault indication is given audibly and visually at the control and 

control panel.  Connect the 

A

mber and 

B

lue of the cable to P

A

 and P

B

 

respectively. Fit a link in the terminals marked EOL. Connect the battery. 
The unit should bleep. This will be repeated every 10 secs.. Re-assemble 
the unit onto the back box. Refit the glass - the sounder will give a double 
whoop within 10 secs. to confirm correct installation. Refit and secure the 
front cover. If on fitting the glass and cover a long tone followed by double 
bleeps every 5 secs. this indicates that there is a problem on the previous 
section. This could be: a short or open circuit on the cable, a reverse 
connection, no battery in the previous unit or no EOL link fitted. 
At the next unit connect the 

A

mber and 

B

lue of the cable from the End of 

Line unit to E

A

 and E

B

 respectively of this unit. Connect the 

A

mber and 

B

lue of the cable leading towards the control panel to P

A

 and P

B

 

respectively. Reassemble the unit as above and check for the double 
whoop on this unit.

Repeat the above procedure at each unit. Do 

NOT 

start to connect the next 

call point until you have heard the double whoop confirmation. At the 
control panel connect 

A

mber and 

B

lue to E

A

 and E

B

 respectively. Ensure 

that the keyswitch is in the RESTART position. Connect the batteries 
(observe the correct polarity). The green system healthy LED should start 
to flash within 10 - 15 secs.. Fit the control panel front onto its back box. If 
the green LED does not flash check the batteries and cable connections in 
the control and the first call point.

can be caused 

by exhausted or partially exhausted batteries, cable connections or cable 
damage. If fault indication occurs on installation or on extending the system it 
could be that the end of line link is not fitted or two have been fitted.
Switch to TEST MODE, any call point with a partially exhausted battery will 
give a single high pitched bleep at 5 sec. intervals. Remove the callpoint and 
replace the battery while in TEST MODE.  

All Callpoint and Control panel 

batteries should be changed.

 

A double high pitched bleep every 5 secs. indicates that there is a cable fault 
between the bleeping unit and the next unit towards the end of line. This 
could also indicate a totally exhausted battery in the next unit.
Any battery replacements or cabling alterations should be done with the 
keyswitch in TEST MODE otherwise it will be necessary to follow the 
installation procedure above. 
If only part of the system is sounding as a fire condition and it is not possible to 
silence it from the control this would indicate that a cable has been damaged 
and it is not possible for the silence signal to be received. In this case it will be 
necessary to remove the batteries from the sounding call points and follow 
the installation procedure above.
NOTE: The GX32CIE is not able to silence smoke alarms that are still 
sensing smoke. If it is not possible to silence the call points beyond this 
detector this would indicate that some of the batteries are approaching the 
battery fail point. It will be necessary to clear the smoke first.

GX32 Battery Powered Fire Alarm System

Pre-wired do not alter

Pre-wired do not alter

Pre-wired
do not alter

Battery connections

Keyswitch
connections

E.O.L link must be fitted
to last call point on system

W:\Tech\Gemini GX32\Common\Installation Instructions\60074.cdr Page 1 Sep 2009 Iss 2

Amber

A

m

b

e

r

A

m

b

e

r

Amber

Amber

Blue

B

lu

e

B

lu

e

Blue

Blue

Black

Red

P

P

B

at

te

ry

- +

GX32SMi

GX32S/1

GX32 is available in kit form but 
individual components can be 
purchased as required.

GX32KIT400

1 x Gx32CIE Control Panel
4 x Gx32MCP Callpoint/sounders
GX32CAB140 140m twin cable
4 x CABCLIP5RBK 100 cable clips

GX32KIT402

1 x Gx32CIE Control Panel
4 x Gx32MCP Callpoint/sounders
2 x GX32SMi Ionisation smoke alarms
GX32CAB140 140m twin cable
4 x CABCLIP5RBK 100 cable clips

All kits and individual items are supplied 
with batteries and fixing screws etc..

NOTE

Smoke alarms, where fitted, can 
only be used between callpoint/
/sounder units. Only one can be 
fitted between each as shown. Thus 
32 smoke alarms would require 32 
callpoint/sounder units.
Smoke alarms cannot be used at 
the end of line.
Smoke alarms are provided with a 
GX32S/1 termination unit to provide 
the necessary termination 
resistance for the GX32 system

www.hoyles.com