37
6.2
Safety temperature limiter - Reset
Fig. 34
If the boiler temperature rises too high (>100 °C), the system is switched off by the safety temperature limiter (STL)
by means of a mechanical lockout.
The malfunction must first be unlocked on the safety temperature limiter, then on the control panel.
Fig. 1STL reset
-
Open the terminal box according to chapter 4.3
-
Unscrew the protective cap
-
Reset the STL
Fig. 2Reset on the control panel
- Press the
reset key
on the control (first remove the cover): the boiler is ready for operation again once the boiler
water temperature is less than 80 °C.
4 213 787 / 01
MAInTEnAnCE