28
Control Board (CB) Setting Menu
Category
No. Item
Range
IM-500SAB
Default
Water Tank
Ice Control
& Harvest
Cycle Low
Temperature
Control
74 Water Tank Ice Control Lower Temperature
See CB Setting 70, 71, 72, 74 description above.
Harvest Cycle Low Temperature Control
If control board thermistor temperature at the begin-
ning of harvest cycle is equal to or less than the
harvest cycle low temperature control setting, hot
gas valve repeatedly energizes for 40 seconds then
de-energizes for 40 seconds to promote a balanced
harvest across the evaporator plate.
0 to 40°C
(1°C increments)
27
D. Control Board Information Display
1) With unit on, press and hold the "SERVICE 1" button for 3 seconds. Display changes to
"n1".
2) Use the "SERVICE 1" and "SERVICE 2" buttons to move through the list.
3) Press the "RESET" button to view the item’s value.
4) Press the "RESET" button to return to list.
5) Display returns to normal if no buttons are touched for 20 seconds.
Control Board Information Display
No. Item
Description
History Cleared by
Pressing and Holding
SERVICE 1 and
SERVICE 2 Buttons
Simultaneously for
5 Sec. when Item Value
is Displayed?
n1
Freeze Cycle Time
During Freeze Cycle: Time since freeze cycle
started.
After Freeze Cycle: Time of previous freeze cycle.
0 to 99 min.
No
n2
Freeze Cycle Completion Rate
During Freeze Cycle: Percent of freeze cycle
completed.
After Freeze Cycle: Percent of previous freeze
cycle completed.
0 to 100%
00 = 100%
No
n3
Current Evaporator (Cube Control) Thermistor
Temperature
°C
No
n4
Current Control Board Thermistor Temperature
°C
No
n5
Water Temperature
Temperature at evaporator (cube control) therm-
istor 30 seconds after pump motor energized in
freeze cycle plus the water temperature correction
value (Control Board Setting 13).
"H" if Higher than 48°F
(9°C)
"L" if 48°F (9°C) or
Lower
No
n6
Current Condenser Thermistor Temperature
Not Applicable to IM-500SAB
°C
No