18
D. Thermistor Check
The cabinet thermistor is used for cabinet temperature control. The Control Module monitors
the thermistor to control system operation. No adjustment is required.
In the event the cabinet thermistor reading is out of range (E0 alarm).
The defrost initiation occurs every 4-hrs. of cumulative compressor run time for 25-min. To
check thermistor resistance, follow the steps below:
1. Unplug the appliance from the electrical outlet.
2. Remove the control box cover.
3. Disconnect and remove the thermistor in question.
4. Immerse the thermistor sensor portion in a glass containing ice and water for 2 to 3 min.
5. Check the resistance between the wires at the thermistor connector. Normal reading is
within 27.0 to 27.9 kΩ. If outside the normal reading, replace the thermistor.
6. Reconnect and replace the thermistor in its correct position.
7. Plug the appliance back into the electrical outlet.
Содержание EF1A-FS
Страница 1: ...FREEZER Service Manual ER1A FS ER2A FS EF1A FS EF2A FS Issued 07 26 2019 Revised 07 14 2020...
Страница 28: ...28 Model Run Capacitor Starting Capacitor ER1A FS 15 F 250 V 250 F 160 V B Wiring Diagram...
Страница 29: ...29 Model Run Capacitor Starting Capacitor EF1A FS 10 F 250 V 150 F 160 V...
Страница 30: ...30 Model Run Capacitor Starting Capacitor ER2A FS 15 F 250 V 250 F 160 V...
Страница 31: ...31 Model Run Capacitor Starting Capacitor EF2A FS 30 F 250 V 200 F 160 V...
Страница 32: ...SERIES 618 Hwy 74 South Peachtree City GA 30269 USA P 800 227 3172 www economyseries com MAN 342 R...