background image

MAN1195-02-EN

Indianapolis, USA  |  Cork, Ireland  |  Calgary, Canada  |  Bangalore, India  |  Oakleigh, Australia  |  Tianjin, China  |  Esteio, Brazil

Please visit our website for a complete listing and to learn more about certified Horner Automation products.
This document is the property of Horner Automation Group, and is subject to change. 

General Specifications

XL7 OCS QUICK START GUIDE

XL7 Overview

1. Touchscreen

2.  Function Keys

3.  MJ1: RS232/ MJ2: 1/2 duplex RS485

4.  Dip Switches

5.   MJ3: RS-232/485 Serial Port

6.  CAN1 Port

7.  PWR: 10-30VDC In

8.  Audio In & Out Ports 

9.  USB 2.0 “A”: Flash Drive

10. LAN 1 & 2 Ports

11.  CAN2 Port

12. USB mini “B”: Programming

13. microSD: Data Storage

1

2

3

4

5

6

7

8

9

10

11

12

13

Built-in I/O

  

NOTE:

 See Precaution #15 on page 4 about USB and grounding. 

Required Power (Steady State)

170mA @ 24VDC

Heater Option

250mA @ 24VDC with heater operation

*Heater Option (Model # plus “-22)

Required Power (Inrush) 

7A for 

< 1

ms @ 24VDC, DC switched

Primary Power Range

10 - 30VDC

Typical Power Backlight 100%

4.848W @ 24VDC

Power Backlight @ 50%

3.792W @ 24VDC

Power Backlight OFF

3.408W @ 24VDC

Relative Humidity

5 to 95% non-condensing

Clock Accuracy

 + / - 20 ppm maximum at 25°C  
(+/- 1 min/month)

Surrounding Air Temp

-10°C to +60°C (-22 Heater Option 
Range is -40°C to +60°C)

Storage Temp

-20°C to +60°C

Weight

2 lbs (907g)

Altitude

Up to 2000m

Rated Pollution Degree

Evaluated for Pollution Degree 2 
Rating

Certifications  
(UL/CE)

North America:   

 https://hornerautomation.com/

certifications/ 

Europe:  

http://www.hornerautomation.eu+

page 1 of 4

Содержание XL7

Страница 1: ... Storage 1 2 3 4 5 6 7 8 9 10 11 12 13 Built in I O NOTE See Precaution 15 on page 4 about USB and grounding Required Power Steady State 170mA 24VDC Heater Option 250mA 24VDC with heater operation Heater Option Model plus 22 Required Power Inrush 7A for 1ms 24VDC DC switched Primary Power Range 10 30VDC Typical Power Backlight 100 4 848W 24VDC Power Backlight 50 3 792W 24VDC Power Backlight OFF 3 ...

Страница 2: ...4 Q3 OUT 3 Q2 OUT2 PWM2 Q1 OUT1 PWM1 MODEL 3 12 DC In 12 DC Out 2 12 bit Analog In J1 Orange Digital Analog In I1 IN1 I2 IN2 I3 IN3 I4 IN4 I5 IN5 I6 IN6 I7 IN7 I8 IN8 H1 HSC1 IN9 H2 HSC2 IN10 H3 HSC3 IN11 H4 HSC4 IN12 A1 Analog IN1 A2 Analog IN2 0V Common 0 10VDC LOOP PWR 20mA I1 I2 I3 I4 I5 I6 I7 I8 H1 H2 H3 H4 A1 A2 OV 12 24VDC OV V Q13 Q12 Q11 Q10 Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1 LOAD LOAD LOAD LOAD ...

Страница 3: ... V IN10 H3 HSC3 V IN11 H4 HSC4 V IN12 J1B 0V Common A1A Univ AI 1 Pin 1 A1B Univ AI 1 Pin 2 A1C Univ AI 1 Pin 3 NC No Connect A2A Univ AI 2 Pin 1 A2B Univ AI 2 Pin 2 A2C Univ AI 2 Pin 3 NC No Connect 12 24VDC I1 I2 I3 I4 I5 I6 I7 I8 H1 H2 H3 H4 0V A1A A1B A1C N C A2A A2B A2C N C 20mA Transmitter T C J3 Orange Green Name Univ AI NC No Connection A3A Univ AI 3 Pin 1 A3B Univ AI 3 Pin 2 A3C Univ AI 3...

Страница 4: ...EMPLACEMENTS DE CLASSE I DIVISION 2 3 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS AND FREE OF IGNITABLE CONCENTRATIONS ATTENTION RISQUE D EXPLOSION NE DECONNECTEZ PAS L EQUIPEMENT A MOINS DE L AVOIR MIS HORS TENSION OU QUE LA ZONE EST CONNUE NON DANGEUREUSE ET NE CONTIENT PAS DE CONCENTRATIONS INFLAMMABLES 4 WARNI...

Отзывы: