background image

MAN0886-03-EN 

 

 

         Specifications / Installation

 

__________________________________________________________________________________________________________________________________________________________________ 

4/28/2009                                                                                                                   Page 1 of 6                                                                                                                             ECN # 950 

 
 

 

 
 
 
 
 
 
 
 
 

Specifications 

 

Specifications 

Digital DC Inputs 

XL103 

XL104 

Digital DC Outputs 

XL103 

XL104 

Inputs per Module 

12 including 4 

configurable HSC inputs 

24 including 4 

configurable HSC inputs 

Outputs per Module 

12 including 2 configurable 

PWM outputs 

16 including 2 configurable 

PWM outputs 

Commons per Module 

Commons per Module 

Input Voltage Range 

12 VDC / 24 VDC 

Output Type 

Sourcing / 10 K Pull-Down 

Absolute Max. Voltage 

35 VDC Max. 

Absolute Max. Voltage 

28 VDC Max. 

Input Impedance 

10 k

 

Output Protection 

Short Circuit 

 

Input Current 

Positive Logic 

Negative Logic 

Max. Output Current 

per point 

0.5 A 

Upper Threshold 

0.8 mA 

-1.6 mA 

Max. Total Current 

 

4 A Continuous 

Lower Threshold 

0.3 mA 

-2.1 mA 

Max. Output Supply 

Voltage 

30 VDC 

Max Upper Threshold 

8 VDC 

Minimum Output Supply 

Voltage 

10 VDC 

Min Lower Threshold 

3 VDC 

Max. Voltage Drop at 

Rated Current 

0.25 VDC 

OFF to ON Response 

1 ms 

Max. Inrush Current 

650 mA per channel 

ON to OFF Response 

1 ms 

Min. Load 

None 

HSC Max. Switching Rate 

10 kHz Totalizer/Pulse,Edges 
5 kHz Frequency/Pulse,Width 

2.5 kHz Quadrature 

OFF to ON Response 

1 ms 

Analog Inputs, Medium 

Resolution 

XL103 

XL104 

ON to OFF Response 

1 ms 

Number of Channels 

Output Characteristics 

Current Sourcing (Pos logic) 

General Specifications 

Input Ranges 

Safe input voltage range 

Input Impedance 

(Clamped @ -0.5 VDC to 12 

VDC) 

0 - 10 VDC 

0 – 20 mA 
4 – 20 mA 

-0.5 V to +12V 
Current Mode: 

100 

 

Voltage Mode: 

500 k 

 

Required Power 

(Steady State) 

500 mA @ 24 VDC 

Required Power (Inrush) 

30 A  for 1 ms @ 24 VDC – DC Switched 

2.5 A for 4 ms @ 24 VDC - AC Switched

 

Nominal Resolution 

%AI full scale 

Max. Over-Current 

10 Bits 

32,000 counts 

35 mA 

Primary Power Range 

10 – 30 VDC 

Conversion Speed 

All channels converted once per ladder scan 

Relative Humidity 

5 to 95% Non-condensing 

Max. Error at 25

°

C (excluding 

zero) 

 

4-20 mA            1.00% 
0-20 mA            1.00% 
0-10 VDC          0.50% 

Operating Temperature 

-10

°

C to +60

°

Terminal Type 

Screw Type,5 mm Removable 

Additional error for temperatures 

other than 25

°

TBD 

CE 

UL 

See Compliance Table at

 

http://www.heapg.com/Pages/TechSupport/ProductCert.html 

Filtering 

160 Hz hash (noise) filter 

1-128 scan digital running average filter 

Weight 

26.5 oz. (.751 kg) 

 

Clock Accuracy 

+/- 35 ppm maximum at 25

°

 C 

(+/- 1.53 Minutes per Month) 

Connectivity 

Serial Ports 

2 Serial Ports – RS232 & RS485 

Ethernet 

10/100-Mbps (XL6e models only) 

USB 

USB Networking Port for communication with PCs and programming Port 

Removable Media 

Removable Media for upto 2 GB of storage for programs, data logging or screen capture 

Smartstix 

Remote IO modules communicating on CAN 

Note:  Highest usable frequency for PWM output is 65 KHz 

 
 
 

XL6/XL6e OCS Models   

HE-XL103 / HEXT350C113  

HE-XL1E3 / HEXT351C113 

Digital DC Inputs / 12 Digital Outputs 

2 Analog Inputs (Medium Resolution) 

XL6/XL6e OCS Models  

HE-XL104 / HEXT350C114 

HE-XL1E4 / HEXT351C114 

24 Digital DC Inputs / 16 Digital Outputs 

2 Analog Inputs (Medium Resolution)

 

Содержание XL6 Series

Страница 1: ...urrent Sourcing Pos logic General Specifications Input Ranges Safe input voltage range Input Impedance Clamped 0 5 VDC to 12 VDC 0 10 VDC 0 20 mA 4 20 mA 0 5 V to 12V Current Mode 100 Ω Voltage Mode 500 k Ω Required Power Steady State 500 mA 24 VDC Required Power Inrush 30 A for 1 ms 24 VDC DC Switched 2 5 A for 4 ms 24 VDC AC Switched Nominal Resolution AI full scale Max Over Current 10 Bits 32 0...

Страница 2: ... mounting clips provided with the OCS until the gasket material forms a tight seal 5 Connect cables as needed such as communications programming power and CsCAN cables to the ports using the provided connectors 6 Begin configuration procedures 3 Panel Cut Out and Dimensions Note Max panel thickness 5 mm Refer to the XL6 User Manual MAN0883 for panel box information and a handy checklist of require...

Страница 3: ...e back cover I O Jumpers I O Jumpers JP are located internally To access remove I O cover of unit Wiring Connectors J1 J2 J3 J4 and I O Jumpers JP1 and JP3 are described in the Wiring and Jumpers section of this document Memory Slot Uses Removable Memory for data logging screen captures program loading and recipes Horner Part No HE MC1 Serial Communications MJ1 RS 232 RS 485 Used for Cscape progra...

Страница 4: ...sed upon the option that is desired Pin MJ1 Pins MJ2 Pins Signal Direction Signal Direction 8 TXD OUT TXD OUT 7 RXD IN RXD IN 6 0 V Ground 0 V Ground 5 5 60mA OUT 5 60mA OUT 4 RTS OUT TX OUT 3 CTS IN TX OUT 2 RX TX IN OUT RX IN 1 RX TX IN OUT RX IN 1 8 5V 60mA Max MJ2 Half Duplex Mode Pin MJ2 Pins Signal Direction 8 TXD OUT 7 RXD IN 6 0 V Ground 5 5 60mA OUT 4 TX OUT 3 TX OUT 2 TX RX IN OUT 1 TX R...

Страница 5: ... Wiring The XL6 can be wired for Positive Logic inputs or Negative Logic inputs Location of I O jumpers JP and wiring connectors J1 J4 Wiring Specifications For I O wiring discrete use the following wire type or equivalent Belden 9918 18 AWG 0 8 mm 2 or larger For shielded Analog I O wiring use the following wire type or equivalent Belden 8441 18 AWG 0 8 mm 2 or larger For CAN wiring use the follo...

Страница 6: ...ely if defective Use Copper Conductors in Field Wiring Only 60 75 C This equipment is suitable for use in Class I Division 2 Groups A B C and D or Non hazardous locations only WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTOR L EQUIPMENT COUPER LE COURANT OU S ASSURE...

Отзывы: