MAN0965-03-EN 

 

 

  Specifications/Installation 

 

10/15/2013                          

No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, LLC. Information in this document is subject to change without notice.

 

 

Page 

4

 of 

6

 

 

 

6.  NETWORK DATA 

Consumed Digital Data

 

– This data is sent from the controller to the SmartBlock.  

For typical applications the I/O configuration 

setup in Cscape will automatically populate this data. 

 For more advanced applications you may use NetPut functions to write this 

data.  Please see the advanced programming guide MAN0880 for more details. 

Bit 

Description 

1-8 

Mode Bit 1 bit per channel 

0 = Voltage Mode 1 = Current mode 

17-20 

Scale Bit 1 bit per channel 

0 = 

10V or 

20mA   1 = 

5V or 4-20mA 

73-80 

Hold Last State 

1 = Hold last State 0 = go to default value 

 
Consumed Analog Data

 

– This data is sent from the controller to the SmartBlock.  

For typical applications the I/O configuration 

setup in Cscape will automatically populate this data. 

 For more advanced applications you may use NetPut functions to write this 

data.  Please see the advanced programming guide MAN0880 for more details. 

Word 

Description 

1-8 

Analog Data 

Data for analog output channels 1 to 8 

9-16 

Default Data 

Analog output default state on error or stop (if selected)  

 

Produced Digital Data

 

– This data is sent from the SmartBlock to the controller.  

Normally this data is mapped into specific 

registers in the I/O configuration in Cscape.

  For advanced applications NetGet functions can be used to obtain this data.  Since this 

data is broadcast to all controllers on the network additional controllers can use NetGet functions to obtain this data as well. 
 

Bit 

Description 

1-32 

Not Used 

33-48 

Status and Diagnostic Data  

49-56 

Firmware Version 

57-64 

Device Class 

– 10 for the DAC207 68 for DAC107 

 
 

7.  SETTING ID SWITCHES 

CsCAN Network IDs are set using the hexadecimal number system from 01 to FD.  The decimal equivalent is 1-253.  Refer to following 
Conversion Table, which shows the decimal equivalent of hexadecimal numbers.  Set a unique Network ID by inserting a small Phillips 
screwdriver into the two identical switches. 

 

NOTE:

  The CsCAN Baud Rate for SmartBlock I/O is fixed at 125KBaud 

 

 

 
 
 
 
 
 
 
 
 
 

Содержание SmartBlock HE579DAC107

Страница 1: ...er Value for Nominal Full Scale 32000 GENERAL SPECIFICATIONS Required Power 24 VDC Voltage Mode 2KΩ 207 145mA 107 105mA Cooling Method Self cooling Relative Humidity 5 to 95 Non condensing Required Power 24 VDC Voltage Mode 2KΩ 207 255mA 107 190mA Altitude for use Up to 2 000m Pollution Degree 2 or lower Voltage Input 10 30 VDS Weight 12oz 340g Operating Temperature 0 to 60 C Atmosphere Free from ...

Страница 2: ...ns Installation 10 15 2013 No part of this publication may be reproduced without the prior agreement and written permission of Horner APG LLC Information in this document is subject to change without notice Page 2 of 6 3 WIRING ...

Страница 3: ...ck I O For advanced operations such as on the fly changes to the output type please see the following chapter on network data and the SmartStix and SmartBlock programming guide To configure SmartBlock I O from Cscape open the Hardware Configuration dialog from the Controller Hardware Configuration menu 1 Select the option for CsCAN I O 2 Click Add 3 Select the SmartStix Tab and select the device t...

Страница 4: ...ed applications you may use NetPut functions to write this data Please see the advanced programming guide MAN0880 for more details Word Description 1 8 Analog Data Data for analog output channels 1 to 8 9 16 Default Data Analog output default state on error or stop if selected Produced Digital Data This data is sent from the SmartBlock to the controller Normally this data is mapped into specific r...

Страница 5: ... 157 9 D 185 B 9 213 D 5 241 F 1 17 1 1 45 2 D 74 4 A 102 6 6 130 8 2 158 9 E 186 B A 214 D 6 242 F 2 18 1 2 46 2 E 75 4 B 103 6 7 131 8 3 159 9 F 187 B B 215 D 7 243 F 3 19 1 3 47 2 F 76 4 C 104 6 8 132 8 4 160 A 0 188 B C 216 D 8 244 F 4 20 1 4 48 3 0 77 4 D 105 6 9 133 8 5 161 A 1 189 B D 217 D 9 245 F 5 21 1 5 49 3 1 78 4 E 106 6 A 134 8 6 162 A 2 190 B E 218 D A 246 F 6 22 1 6 50 3 2 79 4 F 1...

Страница 6: ...uracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need to be followed in the installation of this product For I O wiring discrete use the following wire type or equivalent Belden 9918 18 AWG or larger Adhere to the following safety precautions whenever any type of connection is ...

Отзывы: