HORNER HE-XT100 Скачать руководство пользователя страница 1

MAN0868-01 

 

 

 

 

 

12 October 2007 

 

 

 

 

                    

PAGE 1 

HE-XT100   

 

 

 

 

 

 

 

 

 

 

 

        Specifications / Installation 

 

 
 
 
 
 
 
 
 

1 Specifications 

 

HE-XT100 Specifications 

General Specifications 

Required 
Power 
(Steady State) 

130 mA @ 24 VDC 

Required 
Power (Inrush) 

30 A  for 1 ms @ 24 VDC 

Primary Power 
Range  

10 – 30 VDC 

Relative 
Humidity 

5 to 95% Non-condensing 

Clock Accuracy 

+/- One Minute/Month at 20C 

Operating 
Temperature 

-10

°

C to +60

°

Terminal Type 

Screw Type, 5 mm Removable 

Weight 

12 oz. (340.19 g) 

CE 

UL 

See Compliance Table at : 
 

http://www.heapg.com/Support/compliance.htm

 

 

Panel Cut-Out and Dimensions  

 

Note:  Max. panel thickness: 5 mm. 
 
Refer  to XLt User Manual (MAN0863) for panel box information and 
a handy checklist of requirements. 

 
Note:

   The tolerance to meet NEMA standards is  

±

 0.005” (0.1 mm). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

 
 
 
 

 
 
 
 
 
 
 
 

Ports / Connectors / Cables 

 

Note:

  The case of the XLt is black, but for clarity, it is shown in a lighter gray color.  

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

XLT OCS Model:   HE-XT100

 

3.

62

2

 [9

2m

m

]

3.622 [92mm]

001XLE002

Power Connector 

 

Power Up: 

 

Connect to Earth Ground. 

Apply 10 - 30 VDC. 

Screen lights up. 

 

Torque rating 4.5 – 7 Lb-In 

CAN Connector 

 

Use the CAN Connector when 

using CsCAN network. 

 

Torque rating 4.5 – 7 Lb-In 

To Remove Back Cover: 
 

Unscrew 4 screws located on 
the back of the unit and lift lid.

CAUTION:

  Do not over tighten 

screws when screwing the lid 
back on.

 

 

Memory Slot:    

Uses

 Removable Memory 

for 

data logging, screen captures, 
program loading and recipes. 

Horner Part No.:  HE-MC1 

 

Serial Communications:   
MJ1

:  (RS-232 / RS-485) Use for

Cscape programming and 
Application-Defined 
Communications. 

 
MJ2:

  (RS-232 / RS-485) Use for 

Application-Defined 
Communications.  

Want More Information? 

To download the XLt User Manual 

(MAN0863), refer to 

Technical 

Support

 in this document. 

MJ1

(RS-232 / RS-485)

MJ2

(RS-232 / RS-485)

Memory Slot

 

 

NET 1

(CsCAN)

Power

DIP

Switch