MAN1106-07-EN_XL+_UserManual
M a y 6
t h
, 2 0 2 0
P a g e 87 | 192
4)
Ensure the proper wiring is used for each of the three (3) pins A, B, and C on the
Universal Analog Inputs as seen in the reference image below.
Figure 8.9
–
Loop Power Wiring Details
8.10 Analog Outputs
NOTE: Refer to the datasheet for XL+ OCS model being used for details on jumper settings.
The analog outputs on XL+ OCS devices provide high resolution voltage or current outputs. The
voltage or current selection is controlled with jumpers and configuration settings in Cscape.
NOTE: Each channel can be separately configured for voltage or current mode.
When the controller is stopped, the operation of each output is configurable. The outputs can
hold the state they were in before the controller stopped or they can go to a predetermined
value. By default, analog outputs are set to a value of zero.
CHAPTER 9: HIGH SPEED I/O (HSC / PWM)
Wiring Details:
SPRING CLAMP TERMINALS:
Solid/Stranded wire
—
16-24 awg (1.5-0.2 mm
2
).
Strip Length
—0.31” (8 mm).
SCREW TERMINALS:
Solid/Stranded wire
—
14-28 awg (2.1-0.08 mm
2
).
Strip Length
—0.24” –
0.28 (6-7 mm).
Torque Rating
—
2 in-lbs (0.2 N-m).
Содержание HE-XP7E0
Страница 18: ...MAN1106 07 EN_XL _UserManual M a y 6 t h 2 0 2 0 P a g e 18 192 Figure 3 2 Perimeter Set Studs ...
Страница 21: ...MAN1106 07 EN_XL _UserManual M a y 6 t h 2 0 2 0 P a g e 21 192 3 5 XL Dimensions Figure 3 6 XL OCS Dimensions ...
Страница 106: ...MAN1106 07 EN_XL _UserManual M a y 6 t h 2 0 2 0 P a g e 106 192 10 3 Wiring Figure 10 1 Wiring and Pins ...