Table 6.5
–
PWM Function Registers Map
Register
PWM
HSC
Stepper
%AQ1
PWM1 Duty Cycle (32-bit)
HSC1
Preset Value
Start Frequency
%AQ2
Run Frequency
%AQ3
PWM2 Duty Cycle (32-bit)
HSC2
Preset Value
Accel Count
(32-bit)
%AQ4
%AQ5
PWM Prescale
(32-bit)
--
Run Count
(32-bit)
%AQ6
%AQ7
PWM Period
(32-bit)
--
Decel Count
(32-bit)
%AQ8
%Q1
--
--
Run
%I30
--
--
Ready/Done
%I31
Error
Table 6.6
–
HSC Functions Register Map
Register
Frequency
Totalize
Pulse
Quad
%AI5-6
HSC1 (function) Accumulator
Quad 1 Acc
%AI7-8
HSC2 (function) Accumulator
%AI9-10
HSC3 (function) Accumulator
Quad 2 Acc
%AI11-12
HSC4 (function) Accumulator
%AQ1-2
HSC1 Preset
%AQ3-4
HSC2 Preset
%Q17
Clear HSC1
Clear Quad 1
%Q18
Clear HSC2
Set Quad 1
%Q19
Clear HSC3
Clear Quad 2
%Q20
Clear HSC4
Set Quad 2
6.4 Resource Limits
Table 6.7
–
Resource Limits
Resource
Value
Resource
Value
%S
13
Ethernet
CsCAN, Ping, EGD, SRTP, Modbus TCP
Master (Downloadable Protocol) & Slave,
Ethernet IP, FTP, or HTTP @ 10MBd or
100MBd
%SR
448
CsCAN
125kBd, 250kBd, 500kBd, or 1MBd
%T
16000
Serial Ports
1 RS232, 1 RS485 Ports
%M
16000
IDs Per CsCAN
Network
64 w/o repeat (253 w/ 3 repeaters)
%R
49999
Keypad
5 keys (4 fn keys and a System Key)
%K
5
Display
800 x 480 7” TFT, 65k colors
%D
1023
Screen Memory
64MB
%I
2048
User Screens
1023
%Q
2048
Data Fields Per
User Screen
1023
%AI
512
Ladder Code
1024kB
%AQ