Installation
23
Connecting the communication terminal
Connecting to the RS-485 terminal
The HR-200 has an RS-485 communication terminal.
The applicable electric wire is 0.14 mm
2
to 2.5 mm
2
(AWG 26 to AWG 14).
For the communication cable, use a twisted shielded pair cable.
31 units including this unit can be connected to the host computer. For address settings,
refer to “ RS-485 address setting ” (page 37).
The max. communication cable length is 500 m.
For the terminal treatment of the cable, strip off 11 mm of the insulating coating from the
leading end, and then connect the exposed wires to the terminal.
For the terminal device on the RS-485 communication line, use a terminal resistor (Rt:
120
).
RS-485 communication protocol
The RS-485 communication conditions are shown below.
Reference
For details, refer to communication specifications separately provided.
RS-485
(communication output)
(+)
(
)
Terminal treatment for cable
11 mm
Example of external connection for communication
RS-485
(communication output)
Host computer
Converter
HR-200
Rt
Rt
Item
Condition
Baud rate
19200 bps
Character length
8 bits
Parity
None
Stop bit
1 bit