Storage
Manual_Grid_Power_FNC_en_V3_0
26
7.2.
Storage of Unfilled and Uncharged (UU) and Filled and
Uncharged (FU) grid|power FNC
®
Cells
Note
Ensure that the grid|power FNC
®
cells are sealed with yellow transport plugs.
grid|power FNC
®
cells (UU and FU) can be stored up to three years.
After three years the UU cells must be filled and a recondition charge is necessary, see
Reconditioning on page 48.
If you store the grid|power FNC
®
cells longer than three years,
contact HOPPECKE before you put the cells into operation.
Note
If you want to put the stored grid|power FNC
®
cells into operation, you have to charge the cells
for recommissioning. For information, refer to
9.2 Commissioning of Unfilled and Uncharged (UU)
and Filled and uncharged (FU) grid|power FNC® Cells on page 36