5.5.7 Trigger Reset / Default
In System 6844(RC), a reset or default can be triggered in a differentiated way, in the Sys-
tem or in individual components.
Selection frame:
R E S E T / D E F A U L T
Y / N
Input frame:
R E S E T :
S W = 1
H W = 2
G P S = 3 D E F = 9
> _
A software-reset is triggered by pressing the
1
key followed by
ENT
.
A hardware-reset is triggered by pressing the
2
key followed by
ENT
.
A default of the GPS receiver is triggered by pressing the
3
key followed by
ENT
.
A factory default is triggered by pressing the
9
key followed by
ENT
.
The respective action is triggered approximately 3 seconds after pressing the
ENT
key.
5.5.7.1 Software-Reset (Control Board 6844(RC) only)
This function triggers a software reset of the System 6844(RC) Control Board. All other
Function Boards in the System continue to run (except Function Boards without their own
processor).
This function has no effect on the failsafe-stored data.
5.5.7.2 Hardware-Reset (Complete System)
This function triggers a hardware reset of the whole System 6844(RC). All Function Boards
present in the System 6844(RC) are reset and restarted.
This function has no effect on the failsafe-stored data.
5.5.7.3 Trigger the GPS Receiver Default (GPS only)
This function triggers a default of the onboard GPS receiver located on Control Board
6844(RC). All data stored in the GPS receiver, for example leap second information, are de-
leted and have to be recalculated by the GPS receiver. This may take about 12-13 minutes if
there is satellite reception during this time. Failure of satellite reception may extend this time.
This function has no effect on the data stored fail-safe on Control Board
6844(RC).
5.5.7.4 Factory Default (Control Board 6844(RC) only)
This function triggers a factory default of the entire Control Board 6844(RC) including GPS
receiver (if available). Furthermore, all Function Boards present in System 6844(RC) are re-
set and rebooted.
This function resets
almost every
setting of the Control Board to factory
default values. For exceptions see