2 Product Description
17
2.10 Environmental requirements
Transportation
environment
Requirements
Type of shipping
Waterways, railways, highways, aviation, etc.
Ambient temperature
-40
℃
~+70
℃
Relative humidity
≤
95%, at +40
°
C
Mechanical condition
The vibration should not exceed the following limits:
2Hz
≤
f<9Hz, displacement 7.5mm;
9Hz
≤
f<200Hz, acceleration 20m/s
2
;
200Hz
≤
f<500Hz, acceleration 40m/s
2
;
Storage environment
Requirements
Storage place
Store in a warehouse with air circulation, no harmful gases, no flammable or explosive
materials, and no corrosive materials. Avoid strong mechanical vibrations and shocks;
stay away from strong magnetic fields.
Ambient temperature
-40
℃
~+70
℃
Relative humidity
≤
95%
Mechanical condition
The vibration should not exceed the following limits:
10Hz
≤
f
<
57Hz
,
displacement 0.075mm
;
57Hz
≤
f
<
150Hz
,
acceleration 10m/s
2
;
Working environment
Requirements
Normal operation
Shutdown state
Installation place
Do not install the inverter in an area where flammable or explosive materials are
stored.
The installation site can be indoors or outdoors, preferably in a well ventilated
environment. Avoid direct sunlight, rain and snow to extend the life of the inverter. It is
recommended to install it in a sheltered location. If it is not possible, install an awning.
Ambient temperature
-40 °C ~ +60 °C (after 40 °C, the
maximum continuous input power and
branch current derating 2% per °C)
-40
℃
~+70
℃
Relative humidity
Relative humidity: 5%~95%
Altitude
≤
5000m, more than 4000m must be derated
Mechanical condition
The vibration should not exceed the following limits:
10Hz
≤
f
<
57Hz
,
displacement 0.075mm
;
57Hz
≤
f
<
150Hz
,
acceleration 10m/s2
;
-- This chapter end --