XYR301X-Series Quick setup guide

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 

Modbus 

master 

XYR30

1X 

XYR30
1X 

Set a unique Modbus slave address for each 
XYR301X connected to the Modbus master.  
Example here address = 01. 

Master 

power 

supply 

Connect power:   
(10.8-15.6 VDC) to ‘+’ 
and EARTH to ‘-‘. 
 
XYR3011: 300mA max 
XYR3012: 900mA max 
XYR3013: 900mA max 

 B  A  -  + 

POWER 

ADDRESSING 

x10 

x1 

ON 

 B  A  -  + 

A, B: Connect RS485 

(Modbus) 

RS485 

termination 

switch. 

Up = terminate 

Down = unterminated 

Power and 

Modbus 

connector 

RS485 

Modbus 

master 

XYR 

301X 

XYR 

301X 

XYR 

301X 

 

Termination 
switch up 
(terminated) 

120

 

ø

 2mm

 

EARTH wire

 

XYR301X 

power 

supply 

12VDC

 

power 

power 

power 

power 

modbus 

modbus 

modbus 

earth 

Connection to a Modbus master 

Consult user manual for Modbus addresses. 

XYR 3000 

radio 

Address switches must be 00 for XYR3000 protocol. 

Master 

power 

supply 

Connect power:   
(10.8-15.6 VDC) to ‘+’ 
and EARTH to ‘-‘. 
 

XYR3011: 300mA max 
XYR3012: 900mA max 
XYR3013: 900mA max 

 B  A  -  + 

POWER 

ADDRESSING 

x10 

x1 

ON 

 B  A  -  + 

A, B: Connect RS485  

RS485 

termination 

switch. 

Up = terminate 

Down = unterminated 

Power and 

RS485 

connector 

RS485 

XYR 3000

 

radio 

(RS485-

terminated) 

XYR 

301X 

 

XYR 

301X 

 

XYR 

301X 

 

Termination 
switch up 
(terminated) 

ø

 2mm

 

EARTH wire

 

 

Battery 
12VDC

 

power 

power 

power 

RS485 

RS485 

 

RS485 

 

earth 

Connection to XYR3000 Radio 

Set up using Wireless IO and Gateway Configuration Utility. 

power 

sup 

bat 

XYR301

XYR301X 

XYR301X  XYR301X 