Quick Start Guide for the

WPS Series Wireless Pressure Sensor

Sensing and Control

Issue 1

50095585

m

 WARNING

Honeywell does not recommend using devices for critical 
control applications where there is, or may be, a single point of 
failure or where single points of failure may result in an unsafe 
condition. It is up to the end-user to weigh the risks and benefits 
to determine if the products are appropriate for the application 
based on security, safety and performance. Additionally, it is 
up to the end-user to ensure that the control strategy results in 
a safe operating condition if any crucial segment of the control 
solution fails. Honeywell customers assume full responsibility 
for learning and meeting the required Declaration of Conformity, 
Regulations, Guidelines, etc. for each country in their distribution 
market.

m

 WARNING

RF EXPOSURE

To satisfy FCC RF exposure requirements for mobile transmitting 
devices, a separation distance of 20 cm or more should be 
maintained between the antenna of this device and persons 
during device operation To ensure compliance, operation at 
closer than this distance is not recommended. The antenna 
used for this transmission must not be co-located in conjunction 
with any other antenna or transmitter.

Failure to comply with these instructions could result in 
death or serious injury.

m

 WARNING

The WPS must be installed in accordance with the requirements 
specified in this document in order to comply with the specific 
Country Communication Agency requirements (i.e., FCC, IC, 
ETSI, ACMA, etc.). See Section 3 as this requires choosing the 
correct Country Use Code and thus allowable antenna and/or 
cable usage.

Содержание WPS Series

Страница 1: ...crucial segment of the control solution fails Honeywell customers assume full responsibility for learning and meeting the required Declaration of Conformity Regulations Guidelines etc for each country in their distribution market m WARNING RF EXPOSURE To satisfy FCC RF exposure requirements for mobile transmitting devices a separation distance of 20 cm or more should be maintained between the ante...

Страница 2: ... is targeted at open loop control supervisory control and controls that do not have environ mental or safety consequences As with any process control solu tion the end user must weigh the risks and benefits to determine if the products used are the right match for the application based on security safety and performance Additionally it is up to the end user to ensure that the control strategy shed...

Страница 3: ...Honeywell Sensing and Control i Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 TABLE OF CONTENTS 1 DESCRIPTION 1 1 1 to come ...

Страница 4: ...ii Honeywell Sensing and Control Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 ...

Страница 5: ...Honeywell Sensing and Control iii Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 List of Figures Figure 1 to come List of Tables Table 1 to come ...

Страница 6: ... shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements Earth Ground Functional earth connection NOTE This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements Chassis Ground Identifies a connection to the chassis or frame of the equipment shall b...

Страница 7: ...de 1 2 European Union Usage Usage This product may be used in any of the following European Union nations Table 1 European Union Country ISO 3166 2 letter code Country ISO 3166 2 letter code Austria AT Latvia LV Belgium BE Liechtenstein LI Bulgaria BG Lithuania LT Cyprus CY Malta MT Czech Republic CZ Netherlands NL Denmark DK Norway NO Estonia EE Poland PL Finland FI Portugal PT France FR Romania ...

Страница 8: ...6 Standards Used CSA C22 2 No 30 M1986 CSA C22 2 No 94 M1991 CSA E60079 0 2002 CSA E60079 15 2002 FM 3600 1998 FM 3615 2006 UL 916 1998 CSA C22 2 No 142 M1987 CSA C22 2 No 157 M1992 CSA E60079 1 2002 CSA E61241 0 2002 FM 3610 1999 ANSI ISA 12 12 02 2003 CSA C22 2 No 213 M1987 CSA C22 2 No 60529 2005 CSA E60079 11 2002 CSA E61241 1 2002 FM 3611 2004 UL 50 2003 FM ApprovalsTM 3032450 USA Intrinsical...

Страница 9: ...o 84 C Pressure Temperature Discrete Inputs Corrosion High Level INPUT HLAI Universal I O Enclosure IP66 Standards Used EN 60079 0 2006 EN 61241 1 2004 EN 60079 15 2005 EN 61241 0 2006 IECEx CSA 09 0001X Intrinsically Safe Ex ia IIB T4 Ex tD A20 IP66 T90 oC 40 C to 70 oC Battery 40 C to 80 C dc Supply Pressure Temperature Discrete Inputs Corrosion High Level INPUT HLAI Universal I O Flameproof Ex ...

Страница 10: ...s and used in Category ll 1 G Zone 0 1 4 2 ATEX Conditions for Safe Use Special precautions shall be taken to prevent the surface of the antenna of the WXP SERIES Wireless Transmitter from being electrostati cally charged 1 5 Maximum Working Pressure See WPS Series User s Manual document 50095584 1 6 Radio Certifications Table 3 Radio Certifications Agency Certification Description Federal Communi...

Страница 11: ...d and mounted on outdoor permanent structures with a separa tion distance between the antenna s of greater than 20 cm and a separation distance of at least 100cm from all persons Furthermore when using integral antenna s the WPS Series Wireless Sensor unit must not be co located with any other antenna or transmitter device and have a separation distance of at least 20 cm from all persons 1 6 2 Eur...

Страница 12: ...095585 2 SENSOR MOUNTING 2 1 Weight Model Weight WPS Series 2 lb 3 oz 1 0 kg 2 2 Dimensions Figure 1 Dimensions of WPS Series Wireless Pressure Sensor 234 mm 1 mm 9 21 in 0 04 in 149 mm 1 mm 5 87 in 0 04 in 99 mm 1 mm 3 9 in 0 04 in 95 mm 1 mm 3 74 in 0 04 in 45 mm 1 77 in across flat 31 75 mm 1 25 in hex ...

Страница 13: ... Connection Threads 1 2 NPT Male thread and 1 4 NPT Female thread Swivel The WPS Series sensor body will swivel 350 degrees with respect to the pressure port body to optimize readablilty of the LCD 3 PROCESS INSERTION 3 1 Pressure Sensing 3 1 1 Piping The actual piping arrangement will vary depending upon the process measurement requirements and the sensor model Process connec tions are made to 1 ...

Страница 14: ...ondensate leg and drain at the low point freeze protection may be required here m CAUTION Property damage may result if operating temperature limits of sensor are exceeded Sensor housing must not exceed 85 C 185 F To reduce the temperature of the process that comes into contact with the sensor meter body install impulse piping As a general rule there is a 56 C drop 100 F in the temperature of the ...

Страница 15: ...nd each maintenance procedure after that Mount sensor vertically to assure best accuracy and to obtain optimum R F link performance Position the spirit balance on pressure con nection surface of Sensor body 3 1 4 Sensor Housing Swiveling The WPS Series sensor housing will swivel through a 350 degree range to facilitate easy reading of the LCD display To adjust the swivel mounting 1 Insure that the...

Страница 16: ...or this sensor must be installed to provide a separation distance of at least 20 cm 8 inches from all persons and must not be co located or operating in conjunction with any other antenna or sensor For remote antenna see antenna installation requirements to satisfy FCC RF exposure requirements ATTENTION Federal Communications Commission FCC The WPS Series Wireless Sensors comply with part 15 of th...

Страница 17: ...plug of the antenna to the RP SMA jack on the WPS Tighten the connection until finger tight For straight antennas either 0 dBi or 2 0 dBi attach the antenna ra dome with the two screws provided Insure that the O ring is installed in the grove in the sensor housing If a radome is not used and the antenna is in an exposed location the antenna connector barrel and exposed threads should be protected ...

Страница 18: ...t swivel antenna you can adjust it to improve reception Figure 5 Direct Mount Antenna Option only spot this is included The antenna will tilt through 90 degrees only Rotating will likely be needed as well to orient the antenna vertically Typically pointed straight up gives best performance but your installation may vary Swivel and or tilt antenna for best reception as viewed on the WDM Interface ...

Страница 19: ...on Don t work alone A friend or co worker can save a life if an accident happens Use approved non conducting ladders and other safety equipment Make sure all equipment is in good repair If a tower or mast begins falling don t attempt to catch it Stand back and let it fall If anything such as a wire or mast does come in contact with a power line DON T TOUCH IT OR ATTEMPT TO MOVE IT In stead save a ...

Страница 20: ...SMA connector with a rubber O ring seal which can be used for mounting through an enclosure wall Both connector ports of the lightning arrestor provide equal protection no matter which way it is installed Either port can face the antenna and either port can face the Sensor Refer to the WPS Series Professional Install Guide for further information about lightning arrestors and their installation 4 ...

Страница 21: ...ghtning arrestor options Omnidirectional antennas are vertically polarized and produce a doughnut shaped pattern It is very important to mount the antenna in a vertical not leaning position for optimal performance especially with higher gain antennas Refer to the WPS Series Professional Install Guide for further information about antenna patterns 4 3 7 Magnetic Mounting only spot this type of ante...

Страница 22: ...unted to will affect the radiation pattern so it is suggested that masking tape be used to temporarily at tach the antenna Evaluate R F link performance as described in the WPS Series Professional Install Guide before permanently mounting Permanent mounting Pre clean the surface where the antenna is to be mounted with an alcohol wipe Peel paper protection from adhesive strip and mount to the clean...

Страница 23: ...ealing out door con nections 3 Attach the antenna bracket to the mast using the U Bolts as required 4 Using tie wraps cable ties secure the coax cable to the mast using a tie wrap every ten to twelve inches 25 to 30 cm 5 Follow standard strain relief practice when installing the antenna cable Avoid excessive strain bending kinks or crushing stepping on or placing any weight on cable before during ...

Страница 24: ... must be grounded independant of the antennas using number 10 solid wire This wire must be connected directly to a solid ground It may be the same ground as is used for the antenna tower 4 Refer to the WPS Series Professional Install Guide for further information about lightning arrestors and their installation Drill a hole in the building s wall as close as possible to the equipment to which you ...

Страница 25: ...battery life and avoid unnecessary data transmissions m WARNINGS Risk of death or serious injury by explosion Do not open sensor enclosure when an explosive gas atmosphere is present Batteries must not be changed in an explosive gas atmosphere The sensor enclosure must not be opened when an explosive gas atmosphere is present When not in use the batteries must be stored in a non hazardous area The...

Страница 26: ...HEN AN EXPLOSIVE ATMOSPHERE IS PRESENT 1 On the rear of the WPS Series sensor Unscrew the four captive screws and remove the cover 2 Remove the plastic battery insulator from the positive terminal of on battery Save this insulator for use when removing sen sors from the network before storing them 3 Verify that batteries are oriented with polarity as shown Battery polarity is also shown on battery...

Страница 27: ...r see WPS Series User s Manual Section 5 4 using the WDM Interface 5 2 Display Sequence After power up the sensor does a brief self test of the A D hardware and NVRAM program and data memory Then it proceeds to display the process value PV and units for 3 seconds This sequence will repeat at a rate determined by the publication rate and the LCD display rate 5 3 Provisioning Before the sensor can j...

Страница 28: ...ON REQUIREMENTS 6 1 Certification Drawings Use the following drawings and accompanying notes and text for hazardous locations Any deviation from the installation requirements could void the certification For non hazardous locations you can use the same drawings without the accompanying notes and text Figure 8 EC Declaration of Conformity ...

Страница 29: ...Honeywell Sensing and Control 23 Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 Figure 9 Schedule ...

Страница 30: ...24 Honeywell Sensing and Control Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 Figure 10 Schedule ...

Страница 31: ...Honeywell Sensing and Control 25 Quick Start Guide for the WPS Series Wireless Pressure Sensor ISSUE 1 50095585 Figure 11 CSA Installation Drawings ...

Страница 32: ...icular purpose In no event shall Honeywell be liable for consequential special or indirect damages While we provide application assistance personally through our literature and the Honeywell web site it is up to the customer to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of...

Страница 33: ...cial segment of the control solution fails Honeywell customers assume full responsibility for learning and meeting the required Declaration of Conformity Regulations Guidelines etc for each country in their distribution market m WARNING RF EXPOSURE To satisfy FCC RF exposure requirements for mobile transmitting devices a separation distance of 20 cm or more should be maintained between the antenna...

Страница 34: ...here is a single point of failure or where single points of failure result in unsafe conditions OneWireless is targeted at open loop control supervisory control and controls that do not have environmental or safety consequences As with any process control solution the end user must weigh the risks and benefits to determine if the products used are the right match for the appli cation based on secu...

Страница 35: ...Honeywell Sensing and Control i User Manual for the WPS Series Wireless Pressure Sensor ISSUE 1 50095584 TABLE OF CONTENTS 1 DESCRIPTION 1 1 1 to come ...

Страница 36: ...ii Honeywell Sensing and Control User Manual for the WPS Series Wireless Pressure Sensor ISSUE 1 50095584 ...

Страница 37: ...Honeywell Sensing and Control iii User Manual for the WPS Series Wireless Pressure Sensor ISSUE 1 50095584 List of Figures Figure 1 to come List of Tables Table 1 to come ...

Страница 38: ...th national local electrical code requirements Earth Ground Functional earth connection NOTE This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements Chassis Ground Identifies a connection to the chassis or frame of the equipment shall be bonded to Pro tective Earth at the source of supply in accordance with nati...

Страница 39: ...d into a system regardless of the device manufacturer This interoperability of devices using OneWireless technology is to become an industry standard for automation systems 1 4 About the Sensor The WPS Series Sensor is furnished with an ISA100 11a compliant wireless interface to operate in a compatible distributed ISA100 11a wireless system The sensor will interoperate with any ISA100 11a wireless...

Страница 40: ...US CANADA CA 2 1 2 European Union Country ISO 3166 2 letter code Country ISO 3166 2 letter code Austria AT Latvia LV Belgium BE Liechtenstein LI Bulgaria BG Lithuania LT Cyprus CY Malta MT Czech Republic CZ Netherlands NL Denmark DK Norway NO Estonia EE Poland PL Finland FI Portugal PT France FR Romania RO Germany DE Slovakia SK Greece GR Slovenia SI Hungary HU Spain ES Iceland IS Sweden SE Irelan...

Страница 41: ... IECEx CSA 09 0001X Intrinsically Safe Flameproof Non Sparking Ex ia IIB T4 Ta 70ºC DIP A20 IP66 T90ºC Ex d ia IIB T4 Ta 70ºC DIP A21 IP66 T90ºC Ex nA nL IIC T4 Ta 84ºC DIP A22 IP66 T90ºC Process Connections in Division 2 Zone 2 m Division 2 Zone 2 apparatus may only be connected to processes classified as non hazardous or Division 2 Zone 2 Connection to hazardous flammable or ignition capable Div...

Страница 42: ...communication Operation is subject to the following two conditions 1 this device may not cause interference and 2 this device must ac cept any interference including interference that may cause undesired operation of the device This Class A digital apparatus complies with Canadian ICES 003 French Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada 2 3 3 Radio Frequency ...

Страница 43: ...us for explosive gas atmospheres Part 0 General requirements EN 60079 1 2004 Electrical apparatus for explosive gas atmospheres Part 1 Flameproof enclosure d EN 60079 11 2007 Electrical apparatus for explosive gas atmospheres Part 11 Intrinsic safety i EC 60079 15 2005 Electrical apparatus for explosive gas atmospheres Part 15 Type of protection n EN 61241 0 2007 Electrical apparatus for use in th...

Страница 44: ...a kad šis WPS Series Wireless Transmitters atitinka esminius reikalavimus ir kitas 1999 5 EB Direktyvos nuostatas Nederlands Dutch Hierbij verklaart Honeywell dat het toestel WPS Series Wireless Transmitters in overeenstemming is met de essentiële eisen en de andere relevante bepalingen van richtlijn 1999 5 EG Malti Maltese Hawnhekk Honeywell jiddikjara li dan WPS Series Wireless Transmitters jikk...

Страница 45: ...re when the antenna is used within a potentially explosive atmosphere ap propriate measures must be taken to prevent electrostatic discharge Impact and friction hazards need to be considered according to IEC 600079 0 when the sensor that is exposed to the exterior atmo sphere is made of light metal alloys and used in Category ll 1 G Zone 0 2 6 1 ATEX Conditions for Safe Use Special precautions sha...

Страница 46: ...s network An operator uses the OneWireless WDM Interface to configure the sensor to change operating parameters and to create linkages between blocks that make up the sensor s configuration These changes are written to the sensor when it is authenticated by a security key 3 3 Connecting to Network Use the WDM User Interface to connect your sensor to the OneWireless network Refer to the Wireless De...

Страница 47: ...floating point value There is one AITB per sensor Radio Contains parameters related to radio communication between the sensor and the multimode s Each of these blocks contains parameters that are standard OneWireless sensor defined parameters The AITB and device blocks contain standard parameters common to all ISA100 11a compliant sensors as well as modelI specific parameters The radio block conta...

Страница 48: ...t user settings After a hard reset cold restart any User Settings are replaced with the default User Settings None of the characterization data is user changeable Calibration data from the factory calibration procedure This data is not user eraseable or changeable Program code loaded or updated over the air through the WDM Interface User settings selected through the WDM interface such as publicat...

Страница 49: ... no on off switching so when the batteries are installed the sensor is active See Section 5 for battery considerations and Section 6 for battery replacement procedures 4 3 7 Battery Life The battery life depends on three factors Publication Rate Setting a higher publication rate increases battery consumption LCD display timing Setting the LCD to display continuously or for longer periods will incr...

Страница 50: ... Received Signal strength See Table 5 3 Sensor Link Status Display Table 3 PV Engineering Units Item Displayed Details Pa Pascals kPa KiloPascals Bar Bar Psia Pounds per square inch absolute Psig Pounds per square inch gauge Table 4 Sensor Link Status Display Display Meaning Suggested Action BEST Best strength approx 75 to 25 dBm No action required GOOD Good strength approx 75 to 85 dBm No action ...

Страница 51: ...has crossed the sensor maxumum limit as stored in the characterization data Note this error will clear when the input pressure is measured as 1 or more below the maxi mum limit Crosscheck input pressure with other means if actual pressure is less than the sensor maximum limit the pressure sensor within the unit has probably failed sensor must be replaced 5 3 Battery Considerations As shipped from ...

Страница 52: ...s User Interface with a user account and password having suitable Access Privileges 2 Ensure that the WPS device to be set has been successfully provisioned 3 On the left panel click the sensor name not the channel name 4 On the right panel click on Device Management and scroll down to Battery Estimates 5 Observe the Percent Remaining and Years Remaining 6 If the batteries have just been replaced ...

Страница 53: ...e 2 4 weeks of operation remaining before the batteries expire unless the publication rate is operating at 1 update per second then there is only one week of operation remaining When batteries are removed or expired all sensor configuration data calibration data and program data is retained in the sensor s non volatile memory NVRAM Batteries may be replaced while the Sensor remains connected to th...

Страница 54: ...en not in use the batteries must be stored in a non hazardous area The batteries used in this device may present a risk of fire or chemical burn if mistreated Do not recharge disassemble heat above 100 C 212 F or incinerate Do not expose batteries to water When installing batteries do not snag the battery terminal on the clip or the battery may be damaged Do not apply exces sive force Do not drop ...

Страница 55: ...s or the battery manufacturer s rec ommendations 4 Orient two new batteries with polarity as shown Battery polarity is also shown on battery holder Press two new batteries into the battery clips starting on one end then pressing in the other end Caution Do not scratch the battery outside covering on the sharp edges of the battery clips 5 Re install the rear sensor cover and tighten screws to 1 5 N...

Страница 56: ...ighten snugly with open end wrench Caution Do not overtighten antenna as it could twist in the housing and damage the antenna cable or separate it from the R F board 7 Re install antenna radome fastening it with two screws and tighten screws to 0 8 Nm 7 0 in lb 6 4 Software Updates As required new software may be uploaded over the air into the sensor This procedure may be performed while the senso...

Страница 57: ...rticular purpose In no event shall Honeywell be liable for consequential special or indirect damages While we provide application assistance personally through our literature and the Honeywell web site it is up to the customer to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as ...