W7212, W7213, W7214 ECONOMIZER LOGIC MODULES

63-2596—09

8

SETTINGS AND ADJUSTMENTS

CAUTION

Equipment Damage Hazard.

Excessive force can damage potentiometer 

controls.

Use a small screwdriver or the plastic tool provided 

with the economizer when adjusting all potentiometers 

located on the unit.

Potentiometers with screwdriver adjustment slots, located on 

device face, provide adjustments for several parameters 

(see Fig. 5 for locations on device):

— DCV setpoint.

— Minimum damper position.

— DCV maximum damper position.

— Enthalpy changeover.

— Exhaust setpoint.

Fig. 5. Potentiometer and LED locations (W7212 shown).

Demand Control Ventilation Setpoint

The logic module modulates the outdoor damper to provide 

ventilation based on the 2-10 Vdc DCV input (AQ-AQ1 

terminals). With no cooling signal, the DCV overrides the 

outdoor air damper when ventilation requires additional 

outdoor air.

EXAMPLE: CO2 sensor with 2 to 10 Vdc output range 0 to 

2000 ppm. Two (2) Vdc is equal to 0 ppm, 10 Vdc is equal to 

2000 ppm, threshold is determined to be 1000 ppm. DCV 

potentiometer to be set at 6 Vdc.

Adjust the potentiometer with a small screwdriver by turning 

the pot to the fully CCW then fully CW positions to determine 

the end stops. Set the pot for 6 Vdc in the mid position. 

Adjusting Minimum and Maximum 
Positions

The minimum position is defined by the minimum outdoor air 

flow required in the building during the occupied period. The 

MIN POS and DCV MAX position potentiometers allow the 

installer to set the proper ventilation based on occupancy 

established by ASHRAE standard 62.1. When used with a 

CO2 occupancy sensor the minimum position will modulate 

between the MIN POS pot setting and the DCV MAX pot 

setting based on the CO2 input to the AQ-AQ1 terminals from 

the CO2 sensor located in the space. When a CO2 sensor is 

NOT USED with the unit, the OA dampers will modulate based 

on the actions in Table 1. Setting the DCV maximum position of 

the damper prevents the introduction of large amounts of hot or 

cold air into the space by preventing the dampers from opening 

100% during a call for additional ventilation. On a call for 

cooling AND the OA is good for economizing, the unit will 

override the DCV MAX setting and allow the dampers to drive 

full open.

IMPORTANT

With the DCV maximum position set below the 

minimum position, the minimum position overrides the 

maximum position with the series 2 units.

NOTES:

When the mixed air sensor takes control based on 

an increased requirement for cooling, it overrides 

the DCV maximum position potentiometer and can 

drive the damper full-open.

If the mixed air temperature drops to 45°F, the 

mixed air sensor overrides the DCV and closes the 

damper to protect from freezing the hot or chilled 

water coils. Control returns to normal once the 

mixed air temperature rises to 48°F. Some models 

of the W7212 close the damper fully and others 

close the damper to minimum position. Check the 

label on the box for position of damper on freeze 

protection. If the CO2 sensor should fail, the 

W7212 defaults to DCV maximum, providing mini-

mum ventilation for the maximum design occu-

pancy.

Minimum Position Adjustment

For detailed assistance in minimum position selection 

reference the Economizer Application Guide (form 63-8594) 

Ventilation section. The following provides basic guidelines for 

minimum position selection and adjustment:

IMPORTANT

• Adjust the minimum position potentiometer to allow 

the minimum amount of outdoor air for building efflu-

ents, as required by local codes, to enter the building.

• This procedure requires use of a quality thermometer 

capable of reading to 0.5°F [0.25°C].

NOTE: Make ventilation adjustments with at least a 10°F 

[6°C] temperature difference between outdoor and 

return air.

1.

Calculate the appropriate mixed air temperature, see 

Equation 1.

Equation 1 will be used to set the damper positions for 

MIN POS and DCV MAX. Without a DCV sensor con-

nected to AQ-AQ1, use the MIN POS pot and this proce-

dure to adjust the damper positions for minimum OA 

when the space is occupied. When using a DCV sensor 

you will need to set the MIN POS and DCV MAX posi-

tions using this procedure. DCV MAX will be the same as 

the MIN POS above (without a DCV sensor) and the MIN 

POS will lower than the DCV MAX %.

2.

Disconnect mixed air sensor from terminals T and T1.

3.

Place a jumper across terminals T and T1.

DEMAND CONTROL

VENTILATION SETPOINT

ENTHALPY 

CHANGEOVER SETPOINT 

LED LIGHTS WHEN

DEMAND CONTROL

VENTILATION INPUT

IS ABOVE SETPOINT

EXHAUST 

FAN SETPOINT 

LED LIGHTS 

 WHEN EXHAUST 

 CONTACT IS MADE 

MINIMUM DAMPER 

POSITION SETTING 

M20604B

N1 

P1 

T1 

2V 

2V 

2V 

SR 

SO 

AQ 

C

D

Free 

Cool 

10V 

EXH 

DCV 

EXH 

Set 

10V 

DCV 

Max 

10V 

DCV 

Set 

Min 

Pos 

Open 

AQ1 

SO+ 

SR+ 

MAXIMUM DAMPER 

 DEMAND CONTROL 

VENTILATION SETPOINT 

LED LIGHTS WHEN 

OUTDOOR AIR IS 

SUITABLE FOR 

FREE COOLING 

B

A

D

E

C

W7212C modules have 

the "E" enthalpy curve

Содержание W7212

Страница 1: ...damper position potentiometers with compressor staging Solid state enthalpy or dry bulb changeover control Terminals included for switching between Occupied and Unoccupied operation Terminals included for connecting optional S963B1128 Remote Potentiometer for remote minimum damper position control LED indicates when free cooling is available LED indicates when module is in DCV mode LED indicates w...

Страница 2: ...ed unoccupied control DCV CO2 operation CO2 sensor failure mode and DCV maximum DCV MAX Occupied Unoccupied overrides minimum damper position setting when building is unoccupied On CO2 sensor failure the damper outdoor damper defaults to DCV maximum position See table 1 for economizer functions based on occu pancy CO2 input and damper positions for adjustments of potentiometers for MIN POS and DCV...

Страница 3: ...ienced service technician 4 After installation is complete check out product operation as provided in these instructions 5 When adding a CO2 sensor DCV sensor in the field the MIN POS and DCV MAX position potentiometers must be adjusted by the installer The MIN POS potenti ometer must be closer to the fully CCW position that the DCV MAX potentiometer for the damper to modulate beteen the two setti...

Страница 4: ...roper operation Demand Control Ventilation The DCV CO2 sensor must provide a 2 10 Vdc output Less than 1Vdc input assumes a sensor failure and the action of the outdoor air dampers defaults to 1Vdc operation in Table 1 The DCV CO2 modulates the outdoor damper to provide ventilation based on occupancy The DCV setpoint potentiometer is adjusted to provide ventilation based on the output of the CO2 s...

Страница 5: ... have control of the changeover valve To provide the logic module with the information necessary for proper information there must be a connection to the logic module O B terminal This terminal alerts the logic module as to when the system operates in cooling the only time the economizer is used IMPORTANT During heating applications with defrost make sure to break the connection to the economizer ...

Страница 6: ...nly to dry bulb temperature use only in dry arid climates and only in single dry bulb changeover Do not use the C7660 in differential dry bulb applications The logic module functions as a true first stage of cooling providing maximum energy economy during the cooling cycle It automatically locks out free cooling during heating holding the outdoor air damper at the minimum position setting or if us...

Страница 7: ...position High Free Cooling LED Off Low On On On On Minimum position Closed On Off On Off Off Off Off Off Low Free Cooling LED On High On On On Off Modulatingc between min position and full open Modulatingc between closed and full open On Off Off Off Off Off Off Off Minimum position Closed Above set DCV LED On High Free Cooling LED Off Low On On On On Modulatingd between min position and DCV maximu...

Страница 8: ...m position overrides the maximum position with the series 2 units NOTES When the mixed air sensor takes control based on an increased requirement for cooling it overrides the DCV maximum position potentiometer and can drive the damper full open If the mixed air temperature drops to 45 F the mixed air sensor overrides the DCV and closes the damper to protect from freezing the hot or chilled water c...

Страница 9: ...lected curve will allow the dampers to open for free cooling temperature and humidity conditions to the right of the curve will return the OA damper to minimum position this is either MIN POS if using a CO2 sensor or DCV MAX if a CO2 sensor is NOT used Differential Enthalpy Changeover Setting Differential enthalpy control uses two C7400 Enthalpy Sensors connected to one logic module The logic modu...

Страница 10: ...ROL POINT APPROX F C AT 50 RH 73 23 70 21 67 19 63 17 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45 7 45 7 50 10 50 10 55 13 55 13 60 16 60 16 65 18 65 18 70 21 70 21 75 24 75 24 80 27 80 27 85 29 90 32 95 35...

Страница 11: ... 3 4 3 6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45 7 45 7 50 10 50 10 55 13 55 13 60 16 60 16 65 18 65 18 70 21 70 21 75 24 75 24 80 27 80 27 85 29 90 32 95 35 100 38 APPROXIMATE DRY BULB TEMPERATURE F C A A B B C C D D M23879A R E L A T I V E H U M I D I ...

Страница 12: ...EMS OR SINGLE STAGE COOLING THERMOSTATS T7300 TERMINALS A1 AND A2 ARE CONNECTED WHEN COMMERCIAL THERMOSTAT IS IN THE OCCUPIED MODE EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE M20716F S 1 2 3 2 4 5 5 C7400 OUTDOOR AIR ENTHALPY SENSOR L1 HOT L2 FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP T7300 Q7300 THERMOSTAT 1 C G W1 A2 A1 Y1 Y2 R W2 RC RH G X W1 Y1 Y2 W2 A1 A2 COOL 2 N1 P1 T1 SR SO...

Страница 13: ...ERED BY THE SAME TRANSFORMER AS TERMINAL AUX IF NOT USE AN ISOLATION RELAY TO POWER N FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE M13657B S 1 2 3 2 4 5 C7400 OUTDOOR AIR ENTHALPY SENSOR L1 HOT L2 FAN HEAT 1 HEAT 2 ...

Страница 14: ...A BE SURE THE ECONOMIZER IS POWERED BY THE SAME TRANSFORMER AS TERMINAL A IF NOT USE AN ISOLATION RELAY TO POWER N FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE M13658B S 1 2 3 2 4 5 C7400 OUTDOOR AIR ENTHALPY SENSOR...

Страница 15: ...GE COOLING THERMOSTATS EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE SEE WIRING DIAGRAMS FOR T7350 AND TB7220 TB8220 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE COMMERCIAL THERMOSTAT M13659C S 1 2 3 2 4 5 4 C7400 OUTDOOR AIR ENTHALPY SENSOR UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP COMMERCIAL THERMOSTAT 1 C G W1 Y1 R W2 RC RH G...

Страница 16: ...RMINAL FOR TB7220 OR TB8220 USE A TERMINAL THE TERMINALS ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350 AND TB7220 TB8220 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE COMMERCIAL THERMOSTAT UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP T7...

Страница 17: ...ED TO SR AND SR FOR DIFFERENTIAL ENTHALPY EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350 AND TB7220 TB8220 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE COMMERCIAL THERMOSTAT M13661B 1 2 3 4 5 ST6008 TIMER 1 2 L1 HOT L2 L1 HOT L2 L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 COOL 2 HVAC EQUIPMENT TERMINAL STRIP COMMERCIAL THERMOSTAT 1 C G W1 Y1...

Страница 18: ...S A2 AND A3 ARE CONNECTED WHEN THERMOSTAT IS IN THE UNOCCUPIED MODE SEE T7350 AND TB7220 TB8220 WIRING W7213 B TERMINAL W7214 O TERMINAL M19618E 1 2 3 4 5 4 5 5 L1 HOT L2 FAN HEAT 1 HEAT 2 COOL 1 COOL 2 HVAC EQUIPMENT TERMINAL STRIP T7300 THERMOSTAT 1 C G W1 Y1 Y2 R W2 RC G X O O W1 RH Y1 Y2 A3 A2 W2 S C7400 OUTDOOR AIR ENTHALPY SENSOR O P1 T1 SR SO AQ EF1 5 EF 3 4 2 1 TR MINIMUM POSITION ADJUSTME...

Страница 19: ...PRO IAQ 1 3 Y1 Y2 G RH C Y1 Y2 G R FAN COM HOT COOL 1 COOL 2 W7459 EIM HVAC EQUIP TERMINAL STRIP TR HOT TR1 COMMON RC R 2 3 1 C 1 2 3 0400 2 0174 E 0540 2 SELECT OPTION UNDER THERMOSTAT INSTALLER SETUP VISION PRO IAQ 1 3 Y1 Y2 G RH C Y1 Y2 G R FAN COM HOT COOL 1 COOL 2 W7212 EIM HVAC EQUIP TERMINAL STRIP TR HOT TR1 COMMON RC R 2 3 1 C 1 2 3 V1 T2 N1 N M29973 0400 2 0174 E 0540 2 SELECT OPTION UNDE...

Страница 20: ... CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaults to on board MIN POS potentiometer Place 5 6K ohm resistor across T and T1 Blue sleeve provides input to economizer that the MAT is between 50 55F Jumper TR to 1 call for cooling from the thermostat W7212 only Jumper TR to N p...

Страница 21: ... DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX to fully CCW Motor will drive closed Reconnect jumper to N terminal Adjust DCV MAX and MIN POS pots Motor will drive to the most open position of the pots Adjust DCV MAX and MIN POS pots to fully CCW Remove power from N terminal adjust MIN POS towards CW Motor should not move Adjust DCV MAX towards CW Motor will move...

Страница 22: ...o mid position set enthalpy potentiometer to A Free cool LED turns on Actuator drives to 45 degrees open W7213 Jumper TR to B W7214 Remove jumper from TR and O Free cool LED turns off Actuator drives fully closed Table 4 Checkout for W7212 W7213 W7214 Economizers Connected to Honeywell Actuator Continued Step Checkout Procedure Proper Response ...

Страница 23: ...W7212 W7213 W7214 ECONOMIZER LOGIC MODULES 23 63 2596 09 ...

Страница 24: ... Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 63 2596 09 M S Rev 03 10 Printed in U S A ...

Отзывы: