Honeywell VRW2 Скачать руководство пользователя страница 4

VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES

62-3116—01

4

Application Notes

Accurate valve sizing and adjustment is crucial for efficient 

system operation. Pressure regulated control valves optimize 

hydronic HVAC systems at all load conditions as well as 

balancing the system at design conditions.

Low flow rates maximize coil efficiency, but require pressure 

regulated valves for stable operation.

High temperature change (

Δ

T) is needed to maintain thermal 

transfer at low flow rates, and maximizes efficiencies in chillers 

and condensing boilers.

In new construction, low flow rates at high 

Δ

T reduce the size 

requirements for pumps, chillers, boilers, and piping 

components. In retrofit applications, lower flow rates reduce 

pump energy consumption and peak power requirements.

Pressure regulated control valves work as effectively as 

reverse return piping designs, but use less material.

If a system balancing report is required, coil flow must be 

verified by measuring pressure drop across the coil, not the 

control valve, using the coil manufacturer's specifications. 

Bubble-tight close-off will require use of a resilient-seat 

butterfly valve in series with the load.

Proper Use

These valves are only for use in cold, warm, and hot water 

systems applications with ethylene glycol or propylene glycol 

up to 50% concentration. They are designed for a medium 

temperature range of from -4°F (-20°C) to 228°F (120°C) at a 

maximum pressure of 580 psig (40 bar). VRW2 valves are to 

be operated with supplied multi-turn actuators only.

IMPORTANT

Water should be properly filtered, treated and condi-

tioned according to local conditions and the recom-

mendations of the boiler or chiller manufacturers. The 

installation of strainers and side-stream filters is 

strongly recommended to protect the pressure regula-

tor cartridge

The presence of excessive iron oxide (red rust) in the 

system voids the valve warranty. Rust is highly abra-

sive.

EPDM rubber used in this valve absorbs oil. Do not 

use petroleum-based additives and thoroughly flush 

system to remove petroleum-based cutting oil, solder 

flux, etc. Do not use solvents that will dissolve silicon 

grease

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check ratings given in instructions and on the product to 

ensure the product is suitable for your application.

3.

Installer must be a trained, experienced, licensed service 

technician.

4.

After installation is complete, check out product opera-

tion as provided in these instructions

Preparation

CAUTION

Equipment Damage Hazard

• Foreign particles like sand and metal chips can 

damage valve seals and regulator diaphragm.

• For trouble-free operation of the product, good 

installation practice must include initial system 

flushing, and chemical water treatment. 

• Use of a 50 micron (or finer) system side stream 

filter is recommended and in-line Y-strainers are 

suggested. Remove all sieves before flushing the 

system to avoid trapping dirt in the filters.

• Acceptable antifreeze solutions, with minimum 50% 

water dilution, are diethylene glycol, ethylene glycol, 

and propylene glycol.

• Do not use boiler additives, solder flux and wetted 

materials which are petroleum based or contain 

mineral oil, hydrocarbons, or ethylene glycol 

acetate. If in doubt, consult an HVAC water 

treatment specialist.

• If installing these valves in a new addition, or if 

retrofitting an existing building, do not assume that 

the fluid in the existing piping meets these criteria.

1.

Clean the lines upstream of particles larger than 1/16 in. 

diameter (welding slag, pipe scale and other contami-

nants).

2.

Proceed with installation once the system specifics 

(expansion/contraction of the system and its medium as 

well as operating pressures) are within tolerances.

3.

Eliminate air from system. Free oxygen will corrode iron 

parts.

IMPORTANT

• Ensure that the valve is not in the fully closed position 

when filling the system with water. TURN OFF 

POWER and open manually if necessary.

• Do not exceed maximum pressure differential control 

range for valve.

• Install valve indoors. If valve is installed outdoors, 

water tight protection is required for the actuator.

• If the valve is to be installed in vertical pipe on a 

chilled water system, ensure that the covered elec-

tronics are upwards above the valve spindle, to pre-

vent condensation from entering the electronics. If 

necessary use a socket and ratchet to remove the 

brass nut attaching the mounting bracket to the valve 

body, re-position the Actuator and replace the brass 

nut.

• Even torque on all flange bolts and connecting rods is 

critical to pipe seals.

• Flow arrows must point in the direction of the flow for 

proper operation.

4.

Stem rotation as viewed from above:

a. Clockwise to close.

b. Counterclockwise to open

5.

Valve must be mounted with the actuator/bracket above 

pipe center line. Do not install the valve with the stem 

below horizontal or upside down without NEMA 3, 4, or 

4X actuator enclosure to prevent actuator damage due 

to condensation or leaks. See Fig. 2 and 3.

Содержание VRW2

Страница 1: ...When used in a system with variable speed pump drives 3 way valves and coil bypass lines are not required Systems that utilize the capabilities of properly installed and adjusted pressure independent control valves may qualify for LEED points FEATURES Multi sized bodies from 2 to 6 inch pipes with wafer flanged connections Combination ANSI ASME Class 150 300 pressure rating Controls hot or chilled...

Страница 2: ...low Capacity See Table 1 Body Pressure Rating maximum 580 psig 40 bar at 248 F 120 C Controlled Medium Water or Glycol solutions up to 50 Not suitable for combustible gases oil or steam Fluid Temperature Range 4 to 248 F 20 to 120 C Minimum Differential Pressure See Table 1 Maximum Differential Pressure 58 psid 400 kPa Close off Pressure 101 psid 700 kPa maximum 0 2 leakage Flow Characteristics Eq...

Страница 3: ...75 0 30 0 VRW2L 5 6 DN125 DN150 16 5 8 422 13 1 4 338 7 1 8 180 148 0 70 0 Table 3 Model Selection Valve Regulated Pipe fitting Body Pattern Valve Size Flow Rating Pressure Rating Valve Trim Actuator Secondary Spec Actuator Control Form Description VR Dynamic pressure regulated control valve W Combination size wafer flange 2 2 way J Valve size 2 1 2 and 3 in DN65 and DN80 K Valve size 3 and 4 in D...

Страница 4: ...e a trained experienced licensed service technician 4 After installation is complete check out product opera tion as provided in these instructions Preparation CAUTION Equipment Damage Hazard Foreign particles like sand and metal chips can damage valve seals and regulator diaphragm For trouble free operation of the product good installation practice must include initial system flushing and chemica...

Страница 5: ...ximum Flow Dip Switches so that the actuator limits the valve position to the maximum flow rate required Select the actuator dipswitch setting from Table 4 If adjusting the Dip Switch settings after power has been connected press the Reset Button to input the new setting ORIENTATION OF ACTUATOR ABOVE THE VALVE SPINDLE CORRECT M31296 DN 65 80 INCORRECT DN 65 80 85 85 M29519A M31286 1 ON 2 3 4 5 6 1...

Страница 6: ...8 176 11 1 257 16 21 301 19 0 OFF ON ON ON OFF ON 2 7 84 8 5 4 113 7 1 125 7 9 179 11 3 263 16 59 310 19 6 ON OFF ON ON OFF ON 2 8 86 2 5 4 115 7 3 126 8 0 181 11 4 269 16 97 320 20 2 OFF OFF ON ON OFF ON 2 9 87 7 5 5 117 7 4 128 8 1 184 11 6 276 17 41 329 20 8 ON ON OFF ON OFF ON 3 0 89 1 5 6 119 7 5 130 8 2 187 11 8 282 17 79 339 21 4 OFF ON OFF ON OFF ON 3 1 90 0 5 7 121 7 6 131 8 3 189 11 9 28...

Страница 7: ...6 8 148 9 3 146 9 2 221 13 9 363 22 90 445 28 1 ON ON OFF OFF ON OFF 5 4 108 6 8 149 9 4 146 9 2 221 13 9 364 22 96 448 28 3 OFF ON OFF OFF ON OFF 5 5 108 6 8 150 9 5 147 9 3 221 13 9 365 23 03 452 28 5 ON OFF OFF OFF ON OFF 5 6 109 6 9 151 9 5 147 9 3 221 13 9 366 23 09 455 28 7 OFF OFF OFF OFF ON OFF 5 7 110 6 9 153 9 7 147 9 3 221 13 9 367 23 15 458 28 9 ON ON ON ON OFF OFF 5 8 111 7 0 154 9 7 ...

Страница 8: ...inks once 3 Release the Reset Button The indication LED should remain illu minated 4 Apply the new zero voltage to terminal 3 Any value between 0 7 Vdc 5 Press and release the Reset Button to memorize this value The LED should blink once as confirmation 6 Apply the new maximum voltage to terminal 3 Any voltage between 3 10 Vdc and at least 3 Vdc greater than the zero value 7 Press and release the ...

Страница 9: ...ures At a given shaft position flow through the valve will constant as defined by the formula where ρ is the density of the glycol mix PIN changes constantly in a multi zone system as other valves open and close changing system flow and head pressure according to the characteristics of the supply pump curve Reaction of the mechanical pressure regulator is instantaneous eliminating changes in room ...

Страница 10: ...Analog proportional control refers to direct acceptance of 2 10 Vdc or a 4 20 mA input signal Digital proportional control refers to direct acceptance of 24 Vac pulse width modulated input sig nal Floating control refers to direct acceptance of 24 Vac pulsed open and close commands from a tri state SP3T controller Two position control of non fail safe actuators shall be in the form of 24 Vac power...

Страница 11: ...VRW2 DYNAMIC PRESSURE REGULATING FLANGED CONTROL VALVES 11 62 3116 01 ...

Страница 12: ...Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 62 3116 01 M S 02 10 Printed in U S A ...

Отзывы: