VR8245 AND VR8345 UNIVERSAL ELECTRONIC IGNITION GAS CONTROLS

69-2013

6

WIRING

CAUTION

Disconnect power supply before making 
wiring connections to prevent electrical shock 
or equipment damage.

Follow the wiring instructions furnished by the appliance 
manufacturer, if available, or use the following general 
instructions. Where these instructions differ from the 
appliance manufacturer, follow the appliance 
manufacturer instructions.

All wiring, including insulated quick connect terminals, 
must comply with applicable electrical codes and 
ordinances.

1.

Check the power supply rating on the gas control 
and make sure it matches the available supply. 
Install thermostat and other controls as required.

2.

When the gas control is installed on a hot surface or 
direct spark ignition system, attach the wire adapter 
provided to the wiring terminals. See Fig. 7 for the 
wire terminal location.

3.

Connect control circuit to gas control terminals. See 
Fig. 3 and 8, 9, or 10.

4.

Adjust the thermostat heat anticipator to 0.7, the rat-
ing stamped on the valve operator.

Fig. 7. Install wire adapter for hot surface or direct 

spark ignition systems. Pilot plug must be in the 

valve pilot opening.

Fig. 8. VR8245M/VR8345M,H wiring connections in intermittent ignition system.

M8440A

PV

MV

PV

MV

OFF 

ON 

PILOT GAS SEAL

(PLUG)

WIRE

ADAPTER

L1 

(HOT)

L2

L2

1

L1 

(HOT)

1

4

1

2

3

4

5

6

2

5

6

3

M23470

S8610U

MV MV/PV PV

GND

(BURNER)

24V

GND 24V TH-W

VENT

DAMPER

PLUG

SENSE

SPARK

THERMOSTAT

LIMIT

CONTROLLER

PILOT 

BURNER

GROUND

SENSOR

IGNITER

MV

MV/PV

PV

VALVE

DUAL VALVE COMBINATION

GAS CONTROL

PILOT GAS

SUPPLY

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM CABLE LENGTH 3 FT [0.9 M].

CONTROLS IN 24V CIRCUIT MUST NOT BE GROUND LEG TO TRANSFORMER.

LEAVE VENT DAMPER PLUG CONNECTED.

REMOVE JUMPER AND CONNECT SENSE TERMINAL ON TWO ROD APPLICATION ONLY.

CONTROLLER

COMBUSTION

AIR BLOWER

MOTOR

COMBUSTION

AIR BLOWER

RELAY

AIR

PROVING

SWITCH

Содержание VR8245

Страница 1: ...e conversion factors in Table 2 to convert capacities for other gases APPROVALS American Gas Association Design Certificate L2025007 Canadian Gas Association Design Certificate L2025007 PIPE ADAPTERS Includes two 3 4 to 1 2 inch NPT bushings and one 1 2 to 3 8 inch NPT bushing CROSS REFERENCE See Table 4 for cross reference information INSTALLATION WHEN INSTALLING THIS PRODUCT 1 Read these instruc...

Страница 2: ...ressure Regulator Type Current Draw A Conversion Kits Natural Gas LP LP Natural Gas VR8245M 1 2 x 1 2 Standard 5 393691 394588 VR8345H 3 4 x 3 4 Slow Opening 7 393691 394588 VR8345M 3 4 x 3 4 Standard 7 393691 394588 VR8345Q 3 4 x 3 4 2 Stage 9 396021 396025 Table 4 Cross Reference Universal Replacement Cross Reference Universal Service Part Honeywell White Rodgers Robert Shaw VR8245M2530 VR8204A1...

Страница 3: ... over gas control inlet or outlet 2 Apply moderate amount of good quality pipe com pound to bushing leaving two end threads bare See Fig 1 3 Insert bushing in gas control and carefully thread pipe into the bushing until tight Fig 1 Use moderate amount of pipe compound Location Locate the combination gas control in the appliance vestibule on the gas manifold In replacement applications locate the g...

Страница 4: ...diment trap 4 Apply a moderate amount of good quality pipe com pound do not use Teflon tape to pipe only leaving two end threads bare See Fig 1 On LP installa tions use compound resistant to LP gas 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use wrench on the square ends of the gas control See Fig 3 and 4 When working with an intermi...

Страница 5: ...de a gas tight seal 5 Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms While holding tub ing all the way in slide compression fitting into place engage threads and turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 5 and 6 6 Connect other end of tubing to pilot burner accord ing to pilot burner manufacturer instruc...

Страница 6: ... Connect control circuit to gas control terminals See Fig 3 and 8 9 or 10 4 Adjust the thermostat heat anticipator to 0 7 the rat ing stamped on the valve operator Fig 7 Install wire adapter for hot surface or direct spark ignition systems Pilot plug must be in the valve pilot opening Fig 8 VR8245M VR8345M H wiring connections in intermittent ignition system M8440A PV M V PV M V OFF ON PILOT GAS S...

Страница 7: ... 0 2 VALVE LOAD 120VAC HOT 570A0056 WARNING Explosion hazard Can cause serious injury or death This device can malfunction if it gets wet Never try to use a device that has been wet replace it GND BURNER 24V GND VALVE GND 24V LED L2 HSI HSI L1 SENSE VALVE MPLS MN 55422 SEE INSTRUCTIONS FOR REMOTE SENSE DUAL ROD APPLICATIONS TRIAL TIME NUM OF TRIALS CONFIGURATION PLUG 120VAC NEUTRAL TRIAL TIME 7 SE...

Страница 8: ...er solution anytime work is done on a gas control Gas Leak Test 1 Paint all pipe connections upstream of the gas con trol with a rich soap and water solution Bubbles indicate a gas leak 2 If a gas leak is detected tighten the pipe connection CAUTION Fire or explosion hazard Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flashback in the appli...

Страница 9: ... burner lightoff Make sure that the main burner lights smoothly and that all ports remain lit 2 Check the full rate manifold pressure listed on the appliance nameplate Gas control full rate outlet pressure should match this rating 3 With main burner operating check the control flow rate using the meter clocking method or check pres sure using a manometer connected to the outlet pressure tap on the...

Страница 10: ...e to the safety shutdown or safety lockout tests recommended for the intermittent pilot IP hot surface HSI or direct spark DSI module When different use the procedure rec ommended for the module 1 Turn off gas supply 2 Set the thermostat or controller above room temperature to call for heat 3 Intermittent Pilot Ignition Watch for an igni tion spark at pilot burner either immediately or following p...

Страница 11: ...s that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since these environments can cause the gas control to deteriorate more rapidly the system should be checked more often NOTE If the gas control w...

Страница 12: ...ge tampering bent terminals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The information below will be of assistance in a typi cal gas control application but the specific con trols used and the procedures outlined by the manufacturer or your appliance may differ and requi...

Отзывы: