background image

6    

sensing.honeywell.com

MICRO SWITCH VPX Series

ISSUE F

  

 

32312068

Figure 7. Ground Screw Locations

9.  Spare terminal strip positions are available for making 

junction connections for accessories such as pneumatic 
solenoid valves. The terminal strip will accept 0,5 mm

2

 to 4 

mm

2

 [20-16 AWG] wire. Insert the stripped ends of the wire 

to each connection and tighten the screws to 0,4 Nm ±0,1 
Nm [3.5 in-lb ±1 in-lb].

Figure 8. Spare Terminal Block Locations

Spare terminal blocks

10.  For installations utilizing the UL or cUL certifications, 

install conduit plugs in unused openings. For installations 
utilizing the ATEX/IEC Ex certifications, install blanking 
elements rated Ex db IIC Gb IP66 and Ex tb IIIC Db IP66 in 
unused openings. Conduit size is marked on the inside of 
the housing near the conduit openings.  See Figure 6. 

11.  For installation utilizing the UL or cUL certifications, install 

a conduit seal suitable for Class I Groups B, C and D or 
Class II Groups E, F or G within 450 mm [18 inches] of 
every conduit opening. For installations utilizing the ATEX/
IEC Ex certifications, if an Ex conduit sealing device is 
used, it must be installed immediately at each entry. If an 
Ex cable glad is used, it must be installed per the manufac-
turer’s instructions.

12.  It may be desirable to adjust the cams of the product at this 

point to set the switch points. See the adjustment, repair 
and maintenance section for instructions on how to adjust 
the cams.

13.  Reassemble cover, making sure to align the arrows on the 

cover and the base, per Figure 9. Fasten the (4) socket 
head cap screws that fasten the cover to the base using a 
6 mm hex wrench to 18 Nm ±2 Nm [13.3 ft-lb ±1.5 ft-lb]. 
Screw minimum yield strength: 205 MPa. Confirm with a 
shim or “feeler” gauge that the gap between the cover and 
the base does not exceed 0,038 mm [0.0015 in].

CAUTION

Cover joints must be cleaned before replacing the cover. 
Use care when reassembling the cover in order to prevent 
damage to the switch assembly or to the flange surface.

Figure 9. Cover to Base Alignment

Cover fits only one

orientation. Use arrows on

base and cover for alignment

14.  Perform functional tests.
15.  Actuate the VPX switch several times to ensure smooth 

actuation.

IMPORTANT:

 In units with the 90° spring return feature the 

shaft only rotates ±95°. Use care to insure that total travel does 
not exceed 95° in either direction in the application and during 
set-up.

Содержание VPX Series

Страница 1: ...полните следующие действия 1 Перейдите по адресу http sensing honeywell com hazardousareaswitches 2 Выберите инструкции для изделия в разделе инструкций по установке mWARNING PERSONAL INJURY DO NOT USE these products as safety or emergency stop devices or in any other application where failure of the product could result in personal injury Failure to comply with these instructions could result in ...

Страница 2: ...ding to IEC 60529 HAZARDOUS LOCATION RATINGS 0518 IECEx UL 16 0102X DEMKO 16 ATEX 1733X Compliance with the Essential Health and Safety Requirements has been assured by compliance with CENELEC EN 60079 0 EXPLOSIVE ATMOSPHERES PART 0 EQUIPMENT GENERAL REQUIREMENTS Issue Date 2012 08 01 Revision Date 2013 01 01 CENELEC EN 60079 1 EXPLOSIVE ATMOSPHERES PART 1 EQUIPMENT PROTECTION BY ENCLOSURES d Issu...

Страница 3: ... 切换开关 150VAC 15A 250VAC 10A 250VDC 0 5A 2 本安参数 当产品防爆标志为Ex ia ⅡC T4 Ga或Ex iaD 20 T135时 产品的本安电气参数和内部等效参数详见GYJGYJ16 1394X 防爆合格证附件 3 除非防爆标志为Ex ia ⅡC T4 Ga 否则产品不得在爆炸性环 境开盖 4 应当保持产品外壳表面清洁 以防粉尘堆积 但严禁用压缩空 气吹扫 5 用户不得自行更换该产品的零部件 应会同产品制造商共同解 决运行中出现的故障 以杜绝损坏现象的发生 6 产品的安装 使用和维护应同时遵守产品说明书 GB3836 13 2013 爆炸性环境第13部分 设备的修理 检修 修复和改造 GB3836 15 2000 爆炸性气体环境用电气设备 第15部分 危险场所电气安装 煤矿除外 GB3836 16 2006 爆炸性气体环境用电气设备 第16部分 电...

Страница 4: ...IL 3 0 SC 3 1 year Type A IEC 61508 2 2010 SIRA FSP 16005 00 3 VPX Series Intrensi cally safe proximity switches 500 000 with Single Sided Confidence Limit of 100 SIRA TA 16004 01 50 000 with Single Sided Confidence Limit of 100 SIRA TA 16003 01 SIL 3 0 SC 3 1 year Type A IEC 61508 2 2010 SIRA FSP 16005 00 Notes 1 HFT Hardware Fault Tolerance 2 SC Systematic Capability 3 PTI Proof Test Interval 4 ...

Страница 5: ...screws that fasten the cover to the base using a 6 mm hex wrench 4 Remove the cover and refer to circuit diagram on the inside of the cover or refer to document 32325422 The diagram depicts the available connections of each switch inside the VPX A terminal strip is labeled for each switch connection Figure 4 Circuit Diagram Location Figure 5 Terminal Strip Location Terminal strip connections 5 For...

Страница 6: ...aling device is used it must be installed immediately at each entry If an Ex cable glad is used it must be installed per the manufac turer s instructions 12 It may be desirable to adjust the cams of the product at this point to set the switch points See the adjustment repair and maintenance section for instructions on how to adjust the cams 13 Reassemble cover making sure to align the arrows on th...

Страница 7: ...rotate it to the desired orientation and position it back in place The indicator is adjustable in 90 increments Finally reposition the indicator cover to the desired orientation and tighten the set screws by 4 turns again until the face of the set screw is flush to the cover Tighten to 0 15 Nm 1 3 in lb max Do not over tighten these screws as it may impact the ingress protection of this cover Figu...

Страница 8: ...ts Figure 14 Spacer Spacer 7 When cam adjustment is complete reassemble cover and torque the 4 socket head cap screws that fasten the cover to the base using a 6 mm hex wrench to 18 Nm 2 Nm 13 3 ft lb 1 5 ft lb SPECIAL CONDITIONS FOR SAFE USE Aluminum enclosure Care should be taken to minimize the risk of ignition due to impact or friction Potential electrostatic discharge Clean product only with ...

Страница 9: ...number VPZB1 Figure 16 Accessory Bracket 80 0 3 15 30 0 1 18 30 0 1 18 130 0 5 12 47 10 1 8 0 3 47 10 1 8 0 3 In addition conduit plugs are available in the following sizes Table 3 Conduit Plug Accessories Size Honeywell Part Number Tightening Specification 1 2 14 NPT VPZPA Hand tight and then 1 to 2 full turns using a wrench 3 4 14 NPT VPZPB Hand tight and then 1 to 2 full turns using a wrench M2...

Страница 10: ...nsions CLOSED 75 3 0 min to remove cover 95 8 3 77 Ø 105 8 Ø 4 16 52 0 2 05 4 5 0 18 2 X 32 5 1 28 65 0 2 56 29 0 1 14 140 0 5 51 Conduit Position C Conduit Position D Conduit Position B Conduit Position A 35 36 1 392 140 0 5 51 57 15 2 25 57 15 2 25 35 36 1 392 4 X M6 x 1 8 4 X M8 x 1 25 8 ...

Страница 11: ...Sensing and Internet of Things 11 MICRO SWITCH VPX Series ISSUE F 32312068 ...

Страница 12: ...ly through our literature and the Honeywell web site it is buyer s sole responsibility to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of this writing However Honeywell assumes no responsibility for its use Honeywell serves its customers through a worldwide network of sales ...

Отзывы: