Honeywell V5852A Скачать руководство пользователя страница 1

INSTALLATION INSTRUCTIONS

62-0202-02

V5852A, V5853A, V5862A, 

V5863A  Cartridge Globe Valves

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a 

hazardous condition.

2.

Check ratings given in instructions and on the 

product to ensure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

5.

Do not use Series 3000 actuators on 1/2 in. or 

3/4 in. valves.

WARNING

Severe Scalding Hazard.

Contact with hot liquid can lead to severe 

injury or cause death.

For a pressurized valve, only open with Valve 

Cartridge Replacement Tool. For complete safety, 

release system pressure to the valve body before 

changing cartridge.

CAUTION

Sweat Valve Damage Hazard.

Soldering the valve with the cartridge in place 

can damage the device.

Prior to attaching valve to piping, remove 

cartridge from potential exposure to heat.

IMPORTANT

• Before installing the valve, use the protective 

cover/manual handle to ensure the valve stem 

operates freely. Impaired stem operation can 

indicate a bent stem (due to rough handling). 

This condition can require replacing the valve.

• When installing valves, make sure the flow 

direction is correct by checking the arrow on the 

valve body.

• Mount the valve only with the stem pointing 

upward.

• Leave the protective cover in place until ready to 

attach the actuator.

Location

Select a location where the valve and actuator are 

accessible.

IMPORTANT

Mount all 1/2 in. and 3/4 in. valves in return flow. 

When delta p-values exceed 8.70 psi (60 kPa), 

noise can develop.

Mounting

The valve body should be completely installed in the pipe 

line before the actuator is installed.

IMPORTANT

The insert is packed separately from the 1/2 in. 

and 3/4 in. V5852, V5853 Sweat Valves. The 

valve must be installed and soldered before 

installing the insert in the valve. Torque insert 

between 27 and 44 in.-lb.

1.

Verify pipe size and flow direction for the valve 

being used.

2.

Position the valve for easy actuator installation.

3.

Install the valve using the applicable tools and 

supplies (wrenches, solder, flux, torch or soldering 

iron). Follow standard practices.

Fig. 1. Dimensions of Series 3000 V5862A and 

V5863A Valves in in. (mm).

M19619C

INLET

OUTLET

PORT A

PORT AB

PORT B

V5863 FLOW

V5862A3 FLOW

1 (25)
1-1/4 (32)
1-1/2 (38)

4-1/8 (105)

4-15/16 (125)

5-1/8 (130)

1-5/8 (41)

2 (50)

2-3/16 (55)

2-1/16 (53)
2-7/16 (62)
2-9/16 (65)

3-5/8 (92)
3-5/8 (92)
3-7/8 (98)

B

C

D

E

2-5/16 (58)
2-5/16 (58)

2-11/16 (69)

G

2  (50)

2-3/16 (55)
2-9/16 (65)

F

VALVE SIZE

A (mm)

E

A

C

C

F

B

D

23/32

(18)

G

1/4 (6)

STROKE

MINIMUM CLEARANCE

9-7/8

(250)

FLOW DIAGRAM 

FOR 1, 1-1/4 AND 1-1/2 INCH VALVES