V5055A-F INDUSTRIAL GAS VALVES

7

60-2307—15

Fig. 4. Preparing the pipes.

3.

Remove the protective caps from the ends of the valve. 

Do not attach the valve actuator until the valve body 

installation is complete.

4.

Apply good quality pipe dope resistant to action of 

LP gas, putting a moderate amount on the male threads 

only. Use dope sparingly; if pipe dope lodges on the 

valve seat, it will prevent proper closure. 

5.

Install valve with the gas flow in the direction indicated 

by the arrow on the casting.

6.

Apply a parallel jaw wrench only to the flat next to the 

pipe being inserted (Fig. 5). A wrench applied to the 

valve body itself, or to the end farthest from the pipe 

being inserted, may distort the casting, causing a 

malfunction. Do not use the valve for a lever.

7.

Be sure the gas flow is in the same direction as the 

arrow on the bottom of the valve body.

8.

Use two threaded companion flanges, two gaskets 

(included with valve), and 16 bolts (with washers and 

nuts) for mounting a 4 in.-V5055 Valve. Mount a 

threaded flange and gasket on each end of the valve as 

shown in Fig. 6. Then screw the pipes into the threaded 

flanges. Apply dope sparingly, and use wrenches and 

vises properly as shown in Fig. 4 and 5.

9.

Make sure the power supply is disconnected from 

the valve actuator.

 Then mount the actuator on the 

valve body and complete the electrical and linkage 

connections following the instructions packed with the 

actuator.

OPERATION AND CHECKOUT

Operation

A V5055 Industrial Gas Valve is operated by a V4055, V4062, 

or V9055 Fluid Power Gas Valve Actuator. The valve opens 

when the actuator is energized, and closes when power is 

removed. When closed, the valve seals off against the 

rated close-off pressure with no power applied. For further 

information, refer to the Instructions for the actuator.

Checkout

WARNING

Explosion Hazard.

Can cause serious injury, death or property 

damage.

Do not allow fuel to accumulate in the combustion 

chamber. If fuel is allowed to enter the chamber 

for longer than a few seconds without igniting, an 

explosive mixture could result.

Fig. 5. Installing a 3/4 through 3 in. V5055 Valve.

INCORRECT:

CORRECT:

TWO CLEAN

THREADS,

MODERATE

AMOUNT

OF DOPE

EXCESS DOPE MAY BLOCK

DISK OFF 

VALVE 

SEAT

LOOSE 

CHIPS

NORMAL  

FULL

THREAD

CORRECT:

NORMAL  

FULL 

THREAD

REAM PIPE,

BLOW OUT

CHIPS (TO AVOID

LODGING ON SEAT)

TOO LONG, 

DISTORTS 

VALVE SEAT

INCORRECT:

TOO LONG,

DISTORTS 

VALVE SEAT

M9571

1

1

USE PIPE DOPE RESISTANT TO ACTION OF LP GAS.

CORRECT:

VISE GRIPS END 

NEXT TO PIPE

BEING INSERTED

CORRECT:

WRENCH CORRECTLY

APPLIED NEXT 

TO PIPE BEING 

INSERTED

INCORRECT:

WRENCH HERE 

STRAINS 

VALVE BODY

M9580

Содержание V5055A

Страница 1: ...Valves have a double seal and are used with V4055D E Actuators to provide proof of closure switch and valve seal overtravel interlock V5055D E F Valves are for high pressure applications see Table 1 Seven valve sizes from 3 4 to 3 inches have NPT threaded connections Models are available with BSP PL threads V5055A B C Valves are available in a 4 inch size and have flange connections Most models ha...

Страница 2: ...nly Pipe Size 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 in only V5055A B C available in 4 in size Pipe Threads NPT or BSP PL Threads equivalent to ISO R7 and DIN 2999 Available on inlet and outlet of 3 4 to 3 inch valves Four inch valves have flange connections Pressure Ratings See Table 1 Valve Body Rating 75 psi 517 1 kPa Valve Capacities At 1 in 0 25 kPa pressure drop based on gas with specific gravity...

Страница 3: ...cf h cu m hr 3 4 665 18 8 1 960 27 2 1 1 4 1406 39 8 1 1 2 1717 48 6 2 3620 102 5 2 1 2 4250 120 3 3 5230 148 1 4 V5055A 10200 288 8 4 V5055B C 9180 259 9 M9542 100 2 8 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 1 0 0 25 10 0 2 5 100 0 25 9 8 7 6 5 4 3 2 1 100 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 1000 28 10 000 283 100 000 2...

Страница 4: ... ft for type of gas used 3 Find the capacity in cf h If the capacity is listed in Btu h convert to cfh by the following formula Capacity in cf h Btu h from burner nameplate Btu cu ft from gas utility 4 For gases with specific gravities other than 0 64 multiply the burner cfh by the proper conversion factor See Table 4 Table 4 Gas Conversion Factors 5 Use the corrected burner capacity in cf h when ...

Страница 5: ...08 0 208 0 211 1 223 8 223 8 5 3 4 5 3 4 5 3 4 5 3 4 8 3 8 9 1 4 9 1 4 146 1 146 1 146 1 146 1 212 7 235 0 235 0 2 1 4 2 1 4 2 1 4 2 1 4 2 3 4 2 3 4 2 3 4 57 2 57 2 57 2 57 2 69 9 69 9 69 9 4 13 16 4 13 16 4 13 16 4 13 16 7 19 32 7 19 32 7 19 32 122 2 122 2 122 2 122 2 192 9 192 9 192 9 2 13 16 2 13 16 2 13 16 2 13 16 3 1 2 4 1 2 4 1 2 71 4 71 4 71 4 71 4 88 9 114 3 114 3 DIM A IN MM DIM B IN MM D...

Страница 6: ... must be a trained experienced flame safeguard control technician 4 After installation is complete check out product operations as provided in these instructions WARNING Electrical Shock Hazard and Explosion Hazard Can cause serious injury death or property damage 1 Turn off gas supply before starting installation 2 Disconnect power supply for valve actuator before beginning installation to preven...

Страница 7: ...5 9 Make sure the power supply is disconnected from the valve actuator Then mount the actuator on the valve body and complete the electrical and linkage connections following the instructions packed with the actuator OPERATION AND CHECKOUT Operation A V5055 Industrial Gas Valve is operated by a V4055 V4062 or V9055 Fluid Power Gas Valve Actuator The valve opens when the actuator is energized and c...

Страница 8: ...med by qualified personnel during the initial startup of a burner system or whenever the valve or valve bonnet is replaced see Service Information section It is recommended that this test also be included in the scheduled inspection and maintenance procedures For a periodic inspection test follow steps 1 3 4 5 8 9 10 12 13 16 and 17 Fig 7 Valve leak test 1 De energize the control system to assure ...

Страница 9: ...f the gas supply and disconnect all electrical power to the valve actuator 2 Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems 3 Do not disassemble the valve bonnet assembly the valve seat is not replaceable 4 Failure to properly position and seat the seals in the valve body may result in a hazardous gas leak Scheduled Inspection and...

Страница 10: ...GAS VALVES 60 2307 15 10 Fig 8 Proper positions of valve and bonnet seals in 3 4 through 3 in valves Fig 9 Proper positions of valve and bonnet seals in 4 in valve s M9578 VALVE SEAL BONNET SEAL SMALL SEAL LARGE SEAL M9579 ...

Страница 11: ...11 60 2307 15 ...

Страница 12: ...neywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 V5055A F INDUSTRIAL GAS VALVES ...

Отзывы: