V5055A-F INDUSTRIAL GAS VALVES

60-2307—15

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models:

V5055A Industrial Gas Valve for On-Off service.

V5055B Industrial Gas Valve with characterized guide for 

slow opening, HI-LO-OFF, or modulating service.

V5055C: Same as V5055A but incorporates a double seal. 

Used with the V4055D Actuator to a provide 

proof-of-closure switch and a valve seal overtravel 

interlock.

V5055D: Same as V5055A but for high pressure applications.

V5055E: Same as V5055C but for high pressure applications.

V5055F: Same as V5055E but meets the intent of EN161 

leakage requirements.

Type of Gas: 

 Natural or liquefied petroleum (LP) only.

Pipe Size: 

 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, and 4 in. 

(only V5055A,B,C available in 4 in. size).

Pipe Threads: 

 NPT or BSP-PL Threads (equivalent to ISO 

R7 and DIN 2999). Available on inlet and outlet of 3/4 to 3 inch 

valves. Four inch valves have flange connections.

Pressure Ratings: 

See Table 1.

Valve Body Rating: 

 75 psi (517.1 kPa).

Valve Capacities:  

At 1 in. (0.25 kPa) pressure drop; based 

on gas with specific gravity of 0.64. 

Table 1. Pressure Ratings of Valve-Actuator Combinations.

a

Use a V4055D, V4055E, V4062D, or V9055D (with proof-of-closure switch) with a V5055C,E or F (with double seal) for valve 

seal overtravel interlock.

b

Maximum operating pressure differential.

c

Maximum close-off pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be 

subjected while fully closed, and is independent of the valve body rating.

d

 V5055F available in 1 in., 1-1/4 in., 1-1/2 in. and 2 in. sizes only.

Upstream Tapping and Plug: 

 1 /4 in. NPT or BSP-PL 

is standard.

Downstream Tapping and Plug:

1/4 in. NPT on most domestic models.

1/8 in. NPT on V5055C1182.

Valve

Actuator

V4055A,D

a

V4055B,E,F

a

V4062,V9055

a

Diff.

b

Closeoff

c

Diff.

b

Closeoff

c

Diff.

b

Closeoff

c

psi

kPa

psi

kPa

psi

kPa

psi

kPa

psi

kPa

psi

kPa

V5055A,C

3/4 to 3 in.

5

34.5

15

103.4

15

103.4

15

103.4

5

34.5

15

103.4

V5055A,C

4 in.

3

20.7

15

103.4

5

34.5

15

103.4

3

20.7

15

103.4

V5055B

3/4  to 3 in.

5

34.5

15

103.4

15

103.4

15

103.4

5

34.5

15

103.4

V5055B

4 in.

3

20.7

15

103.4

5

34.5

15

103.4

3

20.7

15

103.4

V5055D,E,F

d

3/4, 1, 1-1/4, 1-1/2 in.

5

34.5

75

517.1

25

172.4

75

517.1

5

34.5

75

517.1

V5055D,E

2, 2-1/2. 3 in.

5

34.5

45

310.3

15

103.4

45

310.3

5

34.5

45

310.3

Содержание V5055A

Страница 1: ...Valves have a double seal and are used with V4055D E Actuators to provide proof of closure switch and valve seal overtravel interlock V5055D E F Valves are for high pressure applications see Table 1 Seven valve sizes from 3 4 to 3 inches have NPT threaded connections Models are available with BSP PL threads V5055A B C Valves are available in a 4 inch size and have flange connections Most models ha...

Страница 2: ...nly Pipe Size 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 in only V5055A B C available in 4 in size Pipe Threads NPT or BSP PL Threads equivalent to ISO R7 and DIN 2999 Available on inlet and outlet of 3 4 to 3 inch valves Four inch valves have flange connections Pressure Ratings See Table 1 Valve Body Rating 75 psi 517 1 kPa Valve Capacities At 1 in 0 25 kPa pressure drop based on gas with specific gravity...

Страница 3: ...cf h cu m hr 3 4 665 18 8 1 960 27 2 1 1 4 1406 39 8 1 1 2 1717 48 6 2 3620 102 5 2 1 2 4250 120 3 3 5230 148 1 4 V5055A 10200 288 8 4 V5055B C 9180 259 9 M9542 100 2 8 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 1 0 0 25 10 0 2 5 100 0 25 9 8 7 6 5 4 3 2 1 100 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 1000 28 10 000 283 100 000 2...

Страница 4: ... ft for type of gas used 3 Find the capacity in cf h If the capacity is listed in Btu h convert to cfh by the following formula Capacity in cf h Btu h from burner nameplate Btu cu ft from gas utility 4 For gases with specific gravities other than 0 64 multiply the burner cfh by the proper conversion factor See Table 4 Table 4 Gas Conversion Factors 5 Use the corrected burner capacity in cf h when ...

Страница 5: ...08 0 208 0 211 1 223 8 223 8 5 3 4 5 3 4 5 3 4 5 3 4 8 3 8 9 1 4 9 1 4 146 1 146 1 146 1 146 1 212 7 235 0 235 0 2 1 4 2 1 4 2 1 4 2 1 4 2 3 4 2 3 4 2 3 4 57 2 57 2 57 2 57 2 69 9 69 9 69 9 4 13 16 4 13 16 4 13 16 4 13 16 7 19 32 7 19 32 7 19 32 122 2 122 2 122 2 122 2 192 9 192 9 192 9 2 13 16 2 13 16 2 13 16 2 13 16 3 1 2 4 1 2 4 1 2 71 4 71 4 71 4 71 4 88 9 114 3 114 3 DIM A IN MM DIM B IN MM D...

Страница 6: ... must be a trained experienced flame safeguard control technician 4 After installation is complete check out product operations as provided in these instructions WARNING Electrical Shock Hazard and Explosion Hazard Can cause serious injury death or property damage 1 Turn off gas supply before starting installation 2 Disconnect power supply for valve actuator before beginning installation to preven...

Страница 7: ...5 9 Make sure the power supply is disconnected from the valve actuator Then mount the actuator on the valve body and complete the electrical and linkage connections following the instructions packed with the actuator OPERATION AND CHECKOUT Operation A V5055 Industrial Gas Valve is operated by a V4055 V4062 or V9055 Fluid Power Gas Valve Actuator The valve opens when the actuator is energized and c...

Страница 8: ...med by qualified personnel during the initial startup of a burner system or whenever the valve or valve bonnet is replaced see Service Information section It is recommended that this test also be included in the scheduled inspection and maintenance procedures For a periodic inspection test follow steps 1 3 4 5 8 9 10 12 13 16 and 17 Fig 7 Valve leak test 1 De energize the control system to assure ...

Страница 9: ...f the gas supply and disconnect all electrical power to the valve actuator 2 Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems 3 Do not disassemble the valve bonnet assembly the valve seat is not replaceable 4 Failure to properly position and seat the seals in the valve body may result in a hazardous gas leak Scheduled Inspection and...

Страница 10: ...GAS VALVES 60 2307 15 10 Fig 8 Proper positions of valve and bonnet seals in 3 4 through 3 in valves Fig 9 Proper positions of valve and bonnet seals in 4 in valve s M9578 VALVE SEAL BONNET SEAL SMALL SEAL LARGE SEAL M9579 ...

Страница 11: ...11 60 2307 15 ...