Actuator's features
•
Proportional control
•
analogue (voltage and current), PWM, 3 points and ON/
OFF
•
Position detecting
•
4-digit display
•
3 buttons to set parameters
•
Position control method to set actuator
2
Installation Instructions
1.
Mount the valve with the arrow in the direction of the
flow
CAUTION!
Mounting it in the wrong direction may damage the
system and the valve itself.
If flow reversal is possible, a non-return valve should be
mounted.
Minimum differential pressure above which the valve begins
to exercise its regulating effect:
2.
To set the flow on the V5004TF use the digital display
and three buttons on the Smart actuator.
When it is switched on, the Zero Detection function
automatically starts: the display shows “Go 0“. Wait
while the actuator is running and the end stroke is
found: finally the display will change to “0”.
To enter the settings browser, press the button MODE.
Press UP and DOWN buttons to select the setting.
Press MODE to show different options and browse
using UP and DOWN buttons. Once the option is found,
press MODE to confirm as the selection.
Startup Pressure
OS-No.
Flow
[I/h]
∆
[kPa]
at 30%
flow
∆
[kPa]
at 50%
flow
∆
[kPa]
at 80% flow
∆
[kPa]
at 100%
flow
∆
[kPa]
V5004TF1050
2000 - 20000
21
25
31
40
600
V5004TF1065
3000 - 30000
26
29
30
30
600
V5004TF1080
3000 - 30000
23
25
30
30
600
V5004TF1100
5500 - 55000
16
20
24
30
600
V5004TF1125
9000 - 90000
21
25
31
35
600
V5004TF1150
15000 - 150000
31
35
41
50
600
V5004TF1200LF
20000 - 200000
31
35
36
40
400
V5004TF1200HF
30000 - 300000
32
37
38
40
400
V5004TF1250LF
30000 - 300000
30
30
33
40
400
V5004TF1250HF
50000 - 500000
38
49
58
65
400
SET1
Input indication selection with internal
control signal
SET2
Control signal selection
SET3
Min. flow rate setting
SET4
Max. flow rate setting
SET5
Setting display mode during operation
SET6
Rotation angle compensation
SET7
Flow rate offset compensation
SET8
Power failure mode
SET9
Flow rate unit selection
SET10
Control curve selection
SET11
Max. voltage control signal
SET12
Min. voltage control signal
SET13
Actuator rotation speed
SET14
Feedback signal selection