INSTALLATION INSTRUCTIONS

Put Bar Code Here

95C-10819—04

V4043H Motorised Zone Valve

APPLICATION

The V4043H valve has been designed to control the flow of 

water in iron and copper pipe systems. Although specifically 

designed for small bore domestic central heating systems, the 

valve can be used in commercial and industrial applications. 

SPECIFICATIONS

Voltage: 

230-240V ~ 50 Hz

Power Consumption: 

6W

Lead Supplied: 

1 metre, 5 core

Operating Temperature Range: 

+5 to +88° C

Maximum Ambient Temperature: 

+52° C

Pipe Fitting Sizes: 

22 mm & 28 mm compression fitting, 3/4” 

& 1” BSP

Dimensions and KV values: 

See diagrams

SPARES AVAILABLE

Powerhead

Part No. 40003916-001

Motor

Part No. 40002737-003

Ball & O-Ring Kit

Part No. 272742A CARD

Fig. 1. Dimensions

Fig. 2. Flow Characteristics

A

B

C

A

B

C

D

87

60

112

117

CLEARANCE

FOR COVER 

REMOVAL

98

28MM

1/2D

1/2D

D

92

1 IN.

22MM

94

1/2 IN.

Содержание V4043H

Страница 1: ...applications SPECIFICATIONS Voltage 230 240V 50 Hz Power Consumption 6W Lead Supplied 1 metre 5 core Operating Temperature Range 5 to 88 C Maximum Ambient Temperature 52 C Pipe Fitting Sizes 22 mm 28 mm compression fitting 3 4 1 BSP Dimensions and KV values See diagrams SPARES AVAILABLE Powerhead Part No 40003916 001 Motor Part No 40002737 003 Ball O Ring Kit Part No 272742A CARD Fig 1 Dimensions ...

Страница 2: ...eparation of at least 3 mm in all poles must be incorporated in the fixed wiring as a means of disconnecting the supply The system must be appropriately fused PLUMBING The valve may be plumbed in at any angle but must not be mounted so that the valve head is below the horizontal level of the pipework In the unlikely event of a leak a safety hazard could result Do not grip the valve head while maki...

Страница 3: ...terminal 4 or 6 at junction box then link terminal 4 to terminal 6 with a link wire S Plan C Plan Fig 3 Wiring Diagram Note If using the V4043H1080 1 BSP or V4043H1106 28mm the white wire must be electrically isolated S Plan only HEATING ZONE VALVE T6360B ROOM STAT L641A CYLINDER STAT BLUE G YELLOW BROWN GREY G YELLOW GREY ORANGE ORANGE BROWN BLUE L L N N 3 E L N E 4 5 ST699 PROGRAMMER BOILER PUMP...

Страница 4: ... pump C Plan or valve S Plan it should get hot COMPLETION Reset both thermostats to temperature required normally 60 C for cylinder thermostat and 20 C for room thermostat Return programmer to Auto or mode selected by householder Full installation wiring and operating instructions for SUNDIAL products are included in every product pack For special wiring diagrams or applications contact Honeywell ...

Отзывы: