background image

INSTALLATION INSTRUCTIONS 

êçóïïèëÛÚóì

 

H1008A,D 

Automatic Humidity Control 

APPLICATION 

The H1008A,D Automatic Humidity Controls with 
Hum   Software are duct mounted and provide 
automatic, low voltage, electronic control of by-pass 
flow-through, powered flow-through, steam and drum 
humidifiers in central heating systems. The H1008D also 
controls heat/energy recovery units and dehumidifiers. 
The H1008A,D are designed to automatically adjust the 
humidity level based on indoor temperature and humidity, 
inferred or measured outdoor temperature and the 
frost factor dial setting. The frost factor setting is used to 
maintain a comfortable humidity level in the home while 
reducing moisture condensation on inside windows. The 
Hum   Software infers the outdoor temperature 
by monitoring equipment cycles and eliminating the need 
for an outdoor temperature sensor when used with gas or 
oil furnaces. Using the C7089H Outdoor Temperature 
Sensor (purchased separately), the H1008A,D also 
provide automatic humidity control for heat pump 
systems.

 

American Lung Association Health 

House Program and Honeywell Working 

Together For Better Air 

Did you know that the average person breathes 3400 
gallons (12,870 liters) of air each day * and spends 90% 
of that day inside?** 

Indoor air quality products from Honeywell are designed 
to help make your home more comfortable  from zoning 
products that allow you to control the temperature in 
individual areas of the home to humidifiers and comfort 
control centers that help balance the moisture content of 
your indoor air. 

Honeywell is proud to be a partner of the American Lung 
Association Health House program, contributing annually 
to the Lung Association. The Health House program 
provides guidelines for constructing homes with 
improved air quality and ventilation. 

For more information on ways to improve the air inside 
your home, please visit the Health House website at: 
www.healthhouse.org, the American Lung Association 
website at: ww.lungusa.org, and the Lung Association 
website in Canada: www.lung.ca or www.poumon.ca. 

The American Lung Association and its Health House 
program do not endorse products. 

For more information about Honeywell Indoor Air Quality 
products, visit: 
http://yourhome.honeywell.com/, or call 
1-800-345-6770 x531. 

*EPA.National Air Quality 1999 Status & Trends. 

**

Indoor Air Pollution, An Introduction for Health Professionals

, EPA, US 

Government Printing Office #1994-523-217/81322.

 

INSTALLATION 

When Installing this Product... 

1.

  Read these instructions carefully. Failure to 

follow them could damage the product or cause a 
hazardous condition.

 

2.

  Check the ratings given in the instructions to make 

sure the product is suitable for your 
application.

 

3.

  Installer must be a trained, experienced service 

technician.

 

4.

  After installation is complete, check out product 

operation as provided in these instructions. 

Use the following specifications for this installation:

 

Electrical Ratings:

 

Power Supply: 24 Vac, 60 Hz. 
Humidifier Control Relay Contacts: 

Inductive: 2A full load, 10A locked rotor. 
Resistive: 2A. 

Thermostat/Furnace Load: 11 mA maximum at 24 Vac.

 

CAUTION 

Voltage Hazard. 
Power supply can cause electrical shock.

 

Disconnect power supply before beginning 
installation.

Содержание Tradeline H1008A

Страница 1: ...t help balance the moisture content of your indoor air Honeywell is proud to be a partner of the American Lung Association Health House program contributing annually to the Lung Association The Health House program provides guidelines for constructing homes with improved air quality and ventilation For more information on ways to improve the air inside your home please visit the Health House websi...

Страница 2: ... is flat after drilling and cutting holes Fig 3 Mount control on return air duct 3 Mount the base on the duct using the four mounting screws provided Tighten the screws until fully seated with no space between the base and the duct See Fig 3 4 Run a low voltage wire from the humidifier and dehumidifier or ventilator for H1008D and equip ment to the control terminals See Fig 5 9 Use either straight...

Страница 3: ...t the humidifier to the two HUM terminals on the H1008A D as shown in Fig 5 through 8 3 In furnace systems with two transformers connect CG to the cooling system transformer common and connect CW to the heating transformer common Be sure G and W connect to the R terminals of both transformers If only one transformer is used leave the jumper on CG and CW See Fig 10 4 To wire the C7089H Outdoor Temp...

Страница 4: ...ÝÑÒÌÎÑÔò ÚßÒ ÌÛÎÓ ÒßÔÍ Ù ßÒÜ ÝÙ ÒÑÌ ËÍÛÜ Ò ÌØ Í ßÐÐÔ ÝßÌ ÑÒò ÛÈÌÛÎÒßÔ ÌÎßÒÍÚÑÎÓÛÎ ÒÑÌ ÐÎÑÊ ÜÛÜò Ú ÑËÌÜÑÑÎ ÌÛÓÐÛÎßÌËÎÛ ÍÛÒÍÑÎ Í ÒÑÌ ËÍÛÜô É ÎÛ ØÛßÌ ÌÛÎÓ ÒßÔÍ É ßÒÜ ÝÉ ÌÑ ÚËÎÒßÝÛò Ú ËÍ ÒÙ ÑËÌÜÑÑÎ ÌÛÓÐÛÎßÌËÎÛ ÍÛÒÍÑÎô ÎÛÓÑÊÛ ÚßÝÌÑÎÇ ÒÍÌßÔÔÛÜ ÖËÓÐÛÎò î ßËÌÑÓßÌ Ý ØËÓ Ü ÌÇ ÝÑÒÌÎÑÔ Ôï øØÑÌ Óïíîçè Ôî ï í ê ÍÑÔßÌÛÜ ÎÛÔßÇ ÝÑÒÌßÝÌÍò ØÛßÌ ÑÒÔÇ ßÐÐÔ ÝßÌ ÑÒ ÍØÑÉÒò Í Ó ÔßÎ É Î ÒÙ ÎÛÏË ÎÛÜ Ò ØÛßÌ ßÒÜ ÝÑÑÔ ÍÇÍÌÛÓ É...

Страница 5: ...ÔÔ Ì ÓÛÍò ÜÑ ÒÑÌ ËÍÛ ÚßÒ ÞÑßÎÜ ØËÓ Ü ÍÌßÌ ÝÑÒÌßÝÌÍ ÑÎ ÝËÎÎÛÒÌ ÍÛÒÍ ÒÙ ÎÛÔßÇò ÝËÌ ÖËÓÐÛÎ ÚÑÎ ÜÛØËÓ Ü Ú ÛÎ ßÐÐÔ ÝßÌ ÑÒò øÜÑ ÒÑÌ ÝËÌ ÚÑÎ ÊÛÒÌ ÔßÌ ÑÒ ÍÇÍÌÛÓò ÜÛØËÓ ÌÛÎÓ ÒßÔÍ ÍÉ ÌÝØ ÔÑÉ ÊÑÔÌßÙÛ ÜÛØËÓ Ü Ú ÛÎÍô ØÛßÌñÛÒÛÎÙÇ ÎÛÝÑÊÛÎÇ ËÒ ÌÍ ÑÎ ÛÈÌÛÎÒßÔ ÝÑÒÌßÝÌÑÎÍ ÌØßÌ ÍÉ ÌÝØ Ø ÙØ ÊÑÔÌßÙÛ ÜÛØËÓ Ü Ú ÛÎÍò ÖËÓÐÛÎ ßÒÜ ÜÛØËÓ ÌÛÎÓ ÒßÔÍ ÒÑÌ ÐÎÛÍÛÒÌ ÑÒ Øïððèß ÓÑÜÛÔò ë ÎÑÑÓ ÌØÛÎÓÑÍÌßÌ é Ôï øØÑÌ Ôî ï Î É Ù ÚßÒ ÎÛÔßÇ Ø...

Страница 6: ...re is inferred without the need for an outdoor sensor or measured with optional outdoor sensor by the HumidiCalc Software Indoor humidity and temperature information is measured by sensors located on the back of the control The frost factor set by using the frost factor dial allows for variables in furnace oversizing window insulation and average daily outdoor temperature The Automatic Humidity Co...

Страница 7: ...ture drops Table 4 shows approximate sensor resistance values at various temperatures Test Mode Use the following procedure to place the control in the test mode and call for humidification dehumidification 1 Ìurn the frost factor setpoint dial to the Test position 2 Do one of the following a At the thermostat with the system switch set to Heat and the fan switch to Auto move the tem perature setp...

Страница 8: ...ns Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 http yourhome honeywell com U S Registered Trademark 2006 Honeywell International Inc 69 1185EF 4 M S Rev 07 06 ...

Страница 9: ...s chacune des parties de la maison ou d humidificateurs ou de thermostats évolués qui aident à équilibrer le taux d humidité de l air ambiant Honeywell est fière de s associer au programme Health House de l association pulmonaire américaine American Lung Association et de verser un don annuel à l association Le programe Health House donne des directives sur la construction de maisons saines où la ...

Страница 10: ... ser les vis autotaraudeuses REMARQUE S assurer que la surface de tôle est bien plate après avoir percé les ouvertures Fig 3 Installation du régulateur dans la gaine de reprise 3 Fixer le boîtier à la gaine à l aide des quatre vis de fixation fournies Serrer les vis fermement jusqu à ce qu il n y ait plus d espace entre le boîtier et la gaine Voir la Fig 3 4 Faire passer un fil basse tension de l ...

Страница 11: ...eux bornes HUM des H1008A D comme l illustrent les Fig 6 à 10 3 Dans les systèmes de chauffage à deux transfor mateurs raccorder CG au commun du transforma teur du système de refroidissement et raccorder CW au commun du transformateur de chauffage Il faut s assurer que G et W sont raccordés aux bornes R des deux transformateurs s il n y a qu un transformateur il faut laisser le cavalier entre CG e...

Страница 12: ...Íò ÌÎßÒÍÚÑÎÓßÌÛËÎ ÑÐÌ ÑÒÒÛÔ ÒÑÒ ÚÑËÎÒ ò Í ÔÛ ÝßÐÌÛËÎ ÜÛ ÌÛÓÐ ÎßÌËÎÛ ÛÈÌ Î ÛËÎÛ ÒKÛÍÌ ÐßÍ ËÌ Ô Í ô ÎßÝÝÑÎÜÛÎ ÔÛÍ ÞÑÎÒÛÍ ÜÛ ÝØßËÚÚßÙÛ É ÛÌ ÝÉ U ÔKßÐÐßÎÛ Ô ÜÛ ÝØßËÚÚßÙÛò Í ËÒ ÝßÐÌÛËÎ ÜÛ ÌÛÓÐ ÎßÌËÎÛ ÛÈÌ Î ÛËÎÛ ÛÍÌ ËÌ Ô Í ô ÎÛÌ ÎÛÎ ÔÛ ÝßÊßÔ ÛÎ ÒÍÌßÔÔ ÛÒ ËÍ ÒÛò î ØÇÙÎÑÍÌßÌ ßËÌÑÓßÌ ÏËÛ Ôï øÍÑËÍ ÌÛÒÍ ÑÒ ÓÚïíîçè Ôî ï í ê ÝÑÒÌßÝÌÍ ÜË ÎÛÔß Í ÜK ÍÑÔßÌ ÑÒ ÍÇÍÌ7ÓÛ ÜÛ ÝØßËÚÚßÙÛ ÍÛËÔÛÓÛÒÌ ÔÔËÍÌÎ ò ÎßÝÝÑÎÜÛÓÛÒÌ Í ...

Страница 13: ... ÔßÌÛËÎ ÜÛ ÔKØËÓ Ü ÍÌßÌ ÑË ÔÛ ÎÛÔß Í ÝßÐÌÛËÎ ÜÛ ÝÑËÎßÒÌò ÝÑËÐÛÎ ÔÛ ÝßÊßÔ ÛÎ ÐÑËÎ ÔÛÍ ßÐÐÔ ÝßÌ ÑÒÍ ßÊÛÝ Ü ÍØËÓ Ü Ú ÝßÌÛËÎ øÒÛ ÐßÍ ÝÑËÐÛÎ ÔÛ ÝßÊßÔ ÛÎ ÐÑËÎ ÔÛ ÍÇÍÌ7ÓÛ ÜÛ ÊÛÒÌ ÔßÌ ÑÒ ò ÞÑÎÒÛÍ ÜË Ü ÍØËÓ Ü Ú ÝßÌÛËÎ ÏË ÓÛÌÌÛÒÌ ÍÑËÍ ÌÛÒÍ ÑÒ ÔÛÍ Ü ÍØËÓ Ü ÚÝßÌÛËÎÍ ÞßÍÍÛ ÌÛÒÍ ÑÒô ÔÛÍ ßÐÐßÎÛ ÔÍ ÜÛ Î ÝËÐ ÎßÌ ÑÒ ÜK ÒÛÎÙ Û ÛÌ ÜÛ ÝØßÔÛËÎ ÑË ÝÑÒÌßÝÌÛËÎÍ ÏË ÓÛÌÌÛÒÌ ÍÑËÍ ÌÛÒÍ ÑÒ ÔÛÍ Ü ÍØËÓ Ü ÚÝßÌÛËÎÍ ØßËÌÛ ÌÛÒÍ ÑÒò ...

Страница 14: ...st calculée par déduction il n est donc pas nécessaire d installer un capteur de température extérieure ou mesurée avec un capteur de température extérieure en option par le logiciel HumidiCalc MC Le H1008D met le ventilateur ou le déshumidificateur en marche pour abaisser le taux d humidité intérieure lorsque le point de rosée de la maison dépasse 58 F Les données sur la température et l humidité...

Страница 15: ...puis plus de 24 heures ou encore si le capteur de température extérieure indique plus de 17 C le régulateur est alors en mode d arrêt automatique Le régulateur fonctionnera seule ment si le système de chauffage est sous tension ou encore lorsque la température extérieure est sous 16 C afin d empêcher le climatiseur et l humidificateur de fonctionner simultanément Le régulateur peut passer au mode ...

Страница 16: ...mande de chaleur ou b Mettre le sélecteur du système à Off et le sélecteur du ventilateur à On pour que le venti lateur fonctionne en continu 3 Êérifier l humidificateur et ou le déshumidifica teur le ventilateur est en marche Lorsque l hygrostat est en mode d essai le voyant reste allumé quatre secondes puis s éteint quatre secondes Le voyant clignote tant que l hygrostat est en mode d essai Aprè...

Отзывы: