TR80 - Installation and Operation Guide
54
3.15 BLINDS CONTROL
TR80 can control up to 2 blinds, curtains or shutters. General blind parameters are as
shown below.
3. 15. 1 Blind 1 configuration parameters
Blind type setting detail:
Bit 0 - Angle Control:
0 = up/down positioning only – no slat angle control
1 = up/down posit slat angle control
Bit 1 – Position direct/reverse
0: reverse (up is 0%. Up button changes value 100->0%)
1: direct (up is 100%. Up button changes value 0->100%)
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Default
value
Holding
2400
42401
R/W
Blind Group
Count
400
int
0…2
1
Holding
2401
42402
R/W
Blind adjustment
step size
401
enum
0: 1%
1: 2%
2: 5%
3: 10%
4: 20%
3
Holding
2402
42403
R/W
Blinds angle
adjustment step
size
402
enum
0: 1°
1: 2°
2: 5°
3: 10°
4: 15°
3
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Default
value
Holding
2403
42404
R/W
Blind 1 type
403
bitwise
Bit 0: angle
control
Bit 1: position
direct/reverse
1
Holding
2404
42405
R/W
Blind 1 min pos
404
%
0…100%
0%
Holding
2405
42406
R/W
Blind 1 max pos
405
%
0…100%
100%
Holding
2406
42407
R/W
Blind 1 min
angle
406
°
-180°…180°
-80°
Holding
2407
42408
R/W
Blind 1 max
angle
407
°
-180°…180°
+80°