TR80 - Installation and Operation Guide
52
The group 2 control parameters are explained in below table.
Refer lighting group1 for
explanation.
3. 14. 4 Light Group 3 configuration & control
The group 3 configuration parameters are explained in below table. Refer lighting group1
for explanation.
The group 3 control parameters are explained in below table. Refer lighting group1 for
explanation.
Register
type
Relative
Address
Absolute
Address
Dir
Name
Unit
Range
Default
value
Holding
1302
41303
R/W
Light Group 2 last level
%
0-100%
(255: unknown)
255
Holding
1303
41304
R/W
Light Group 2 last scene
int
0-15
(255: unknown)
255
Input
302
30303
R/W
Light Group 2 new level
%
0-100%
32767
Input
303
30304
R/W
Light Group 2 new scene
int
0-15
32767
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
Parameter
Unit
Range
Default
value
Holding
2310
42311
R/W
Light Group 3
allow dimming
310
enum
0: only on/off
control
1: allow dimming
1
Holding
2311
42312
R/W
Light Group 3 min
level
311
%
0…100%
1%
Holding
2312
42313
R/W
Light Group 3 max
level
312
%
0…100%
100%
Holding
2313
42314
R/W
Light Group 3 max
Scene No
313
int
0-16
4
Register
type
Relative
Address
Absolute
Address
Dir
Name
Unit
Range
Default
value
Holding
1304
41305
R/W
Light Group 3 last level
%
0-100%
255: unknown)
255
Holding
1305
41306
R/W
Light Group 3 last scene
int
0-15
255: unknown)
255
Input
304
30305
R/W
Light Group 3 new level
%
0-100%
32767
Input
305
30306
R/W
Light Group 3 new scene
int
0-15
32767