37
TR80 - Installation and Operation Guide
3. 8. 2 Monitoring
Unit and scale of the external sensor input depend on configured signal type:
Temperature values on Modbus are always in degrees Celsius, even if the user has selected
Fahrenheit for display.
3.9 DO-NOT-DISTURB & MAKE-UP-ROOM
Do-not-Disturb and/ Make-Up-Room functions can be enabled individually. The button on the
TR80 will be enabled only if at least one of these functions are enabled.
Register
type
Relative
Address
Absolute
Address
Dir
Name
Unit
Scale
Default
value
Input
5
30006
R
External input measured value
See
below
See
below
0
Input
6
30007
R
Onboard temp sensor measured
value
°C
0.1
0
Input
7
30008
R
Onboard humidity sensor
measured value
%Rh
1
0
Configuration
Unit
Scale
Raw ohms
Ohms
1
NTC
°C
0.1
Voltage (0-10V or 2-10Vdc)
Percent
0.1
NO contact
0=open, 1=closed
NC contact
0=closed, 1=open
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Type
Range
Default
value
Input
3
30009
R
DnD/MuR
status
-
enum
0: none
1: DnD
2: MuR
0
Holding
2014
42015
R/W
DnD/MuR
enable
16
enum
0: disabled
1: DnD enable
2: MuR enable
3: Dnd/Mur enable
1