TR80 - Installation and Operation Guide
36
3. 7. 4 Active Display Mode
This register allows monitoring of the current user mode.
3.8 SENSORS & EXTERNAL INPUT
3. 8. 1 Configuration
Register
type
Relative
Address
Absolute
Address
Dir
Name
Type
Range
Input
100
30101
R
Active display
mode
enum
0: Dark mode
1: Sleep mode
2: Ready mode
3: Protected mode
4: Setting mode (temp, light etc)
5: Config mode
6: Cleaning mode
7: Pin entry
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Scale
Default
value
Holding
2011
42012
R/W
External
sensor
type
13
enu
m
0: NONE
1: NO contact
2: NC contact
3: 0-10 Vdc
4: 2-10 Vdc
5: Raw Ohms
6: NTC10K
7: NTC20K
0
Holding
2012
42013
R/W
On-board
sensor
temp
offset
14
K
-10.0 … +10.0
K
0.1
0
Holding
2013
42014
R/W
On-board
sensor
humidity
offset
15
%Rh
-10 … +10
%Rh
1
0