background image

TP970-TP973 Pneumatic 

Thermostats 

INSTALLATION 

These instructions cover mounting the thermostat to a wall 
without additional hardware. For replacement of existing 
competitive and older Honeywell thermostats, use the 
appropriate adapter kit and follow instructions packed 
with kit. 

Installation Tools 

The following tools will be useful during calibration check 
and cover installation: 

Part No. 

Description (Fig. 1) 

305965 

Gage, 0 to 30 psi (0 to 207 kPa) 

CCT729A 

Gage Adapter for thermostats with 
gage tap fitting 

CCT735A 

Thermostat Tool 

CCT729A 

305965 

CCT735A 

Fig. 1. Thermostat installation tools. 

INSTALLATION INSTRUCTIONS 

Remote Restrictors 

When remote restrictors are required, (one pipe TP973) 
select from Figure 2. 

SEE CHART FOR BARB SIZE 

FILTER 

INLET 

ALL INLET BARBS 

1/4 IN. (6 MM) 

REMOTE RESTRICTORS 

Part No. 

Orifice 

Body 

Barb Size 

in inches (MM) 

14002913– 

Size in inches 

Color 

–001* 

0.005 

Blue 

1/4 (6) 

5/32 (4) 

–004 

0.005 

Blue 

5/32 (4) 

5/32 (4) 

* One Barb Cap 14003567-001 Furnished with Restrictor 

C3931-1 

Fig. 2. Remote restrictors. 

Piping 

Use 5/32-in. O.D. polyethylene tubing. Connect main and 
branch lines to the backplate, connecting main to the left 
side barb fitting as viewed from the back and branch to the 
right side barb. Leave the third (lower) fitting open, except 
for a three-pipe TP971 Thermostat. 

Mounting 

See Figure 3. If mounting on other than a hollow wall, see 
Installation Instructions 95-5597. 

®U.S. Registered Trademark 
Copyright © 1999 Honeywell Inc.  • 

•  All Rights Reserved 

95-7478EF 

Содержание TP970 Series

Страница 1: ...en remote restrictors are required one pipe TP973 select from Figure 2 SEE CHART FOR BARB SIZE A B FILTER INLET ALL INLET BARBS 1 4 IN 6 MM REMOTE RESTRICTORS Part No Orifice Body Barb Size in inches MM 14002913 Size in inches Color A B 001 0 005 Blue 1 4 6 5 32 4 004 0 005 Blue 5 32 4 5 32 4 One Barb Cap 14003567 001 Furnished with Restrictor C3931 1 Fig 2 Remote restrictors Piping Use 5 32 in O ...

Страница 2: ...or C3946 3 accurate control 5 Follow RECALIBRATION procedures Fig 3 Installing TP970 TP973 without wall box ADJUSTMENTS After installation set the thermostat to the desired setpoint and let the system operate long enough to stabilize The length of time required for stabilization depends on system response time This could be only a few minutes or as long as several hours Make certain that the syste...

Страница 3: ...ibrated 5 Remove the gage and replace cover TP971 1 Remove the thermostat cover and install a 30 psi gage into the gage tap 2 Set the temperature setpoint indicator at the indicated temperature 3 With 13 psi 91 kPa DAY main air pressure turn the DAY left calibration screw see Fig 4 until the gage reads 0 psi 4 Turn the calibration screw in the opposite direction until the gage reads 8 psi 56 kPa p...

Страница 4: ...ES RACCORDS À CRANS B A ENTRÉE FILTRE TOUS LES RACCORDS D ENTRÉE 1 4 po 6 mm RESTRICTEURS À DISTANCE No DE PIÈCE TAILLE DE L ORIFICE COULEUR TAILLE DU RACCORD À CRANS EN PO MM 14002913 EN PO DU CORPS A B 001 0 005 Blue 1 4 6 5 32 4 004 0 005 Blue 5 32 4 5 32 4 UN BOUCHON À CRANS 14003567 001 FOURNI AVEC LE RESTRICTEUR CF3931 1 Fig 2 Restricteurs à distance Canalisations Utiliser du tuyau de polyét...

Страница 5: ...on avec purge de leur étalonnage pour qu on s assure de leur bon fonctionnement Bande proportionnelle La bande proportionnelle BP est réglée en usine à 4 F 2 2 C et ne devrait pas nécessiter de modification en conditions normales de fonctionnement S il faut toutefois modifier la bande proportionnelle suivre les étapes ci dessous pour remettre la bande proportionnelle aux valeurs indiquées dans les...

Страница 6: ...e tourner l indicateur du point de consigne jusqu à ce qu il marque la température indiquée 3 Avec une pression d air de jour à la canalisation principale de 13 psi 91 kPa faire tourner la vis d étalonnage de jour à gauche Fig 3 jusqu à ce que le manomètre indique 0 psi 0 kPa 4 Faire tourner la vis d étalonnage dans le sens opposé jusqu à ce que le manomètre indique 8 psi 1 psi 56 kPa 7 kPa 5 Avec...

Отзывы: