INTRODUCTION
Touchpoint Pro
Pt. No. 2400M2566_1_EN
14
Operating Manual
3.3
TPPR System Key Components
3.3.1
Enclosures and Racks
TPPR can be mounted in various sizes of floor or wall mounted enclosures, or on 19” 5U racks. The floor mounted
enclosures can be unventilated, naturally ventilated, or force ventilated. The fully sealed wall mounted enclosures can hold a
controller or can be a remote terminal without a controller.
If using a 19” rack, the OEM or installer must ensure the installation is at least IP20 / Type 1 / Class 1 (grounded) to mitigate
the risk of electrical shock.
Figure 18.
TPPR Enclosures
3.3.2
TPPR Controller User Interfaces
The TPPR Controller is covered with a protective membrane and houses the touch screen user interface (UI), the alarm
buzzer, the Accept and Reset buttons, and coloured LEDs for Power, Alarm, Fault, and Inhibit.
The controller has four access methods:
•
Control Panel touch screen for normal system operation, maintenance and configuration
•
PC Configuration Software (optional licences) for secure maintenance and configuration over a VPN or cable
•
Webserver (optional licences) allows up to 5 people to securely view events and carry out basic system operation via
an Ethernet connection or the Internet
•
Modbus option
Internal System Interfaces consist of:
•
Two master relays that signal System Failure and System Fault
•
Connections for one SD Card and one USB drive
•
10/100 Mbps Ethernet connection (for networked interfacing)
•
Optional dual RS 485 Modbus RTU interface
Figure 19.
TPPR Controller Cover with Connection Map