Electrical Power Connection and Interfacing
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
36
Technical Handbook
Note 1:
+24 VDC Nominal = Controller Input (18 to 32 VDC) 1.8 VDC (the max voltage drop in the TPPL).
Note 2:
Alarm Terminals 13, 19, 20, and 21 can 24 VDC at 28 W combined this 28 W can instead be used to
increase the power available to field sensors if external audible and visible alarms are not connected. e.g. the 8 sensor
channels would normally have
W of combined available power, but this can be increased to 68.8 W if terminals 13
21 are unused.
Note 3:
You must supply sensors with external power if more than 40 / 68 W total power is required (See Note 2).
Note 4:
Maximum R
loop
resistance for a remote reset/inhibit switch is 18
Ω
, for instance
m of 1 mm
2
shielded
cable.
Note 5:
RLY1 or RLY2 should be configured as "system inhibit relay"
5.2.6
Expansion Module Power Connections
The cables must be fitted through a gland to preserve the IP rating.
Module Label
Terminal
Identifier
Purpose
Remarks
Power
1
+DC
24 VDC
Power Supply In
2
DC
0 VDC
3
Earth
CAN
25
CAN_H
CAN High
Link from Basic Unit
26
CAN_L
CAN Low
Expansion Unit Main Module Connections
Connecting the Expansion Unit to the Basic Unit
TPPL Controller Unit
Main Module
TPPL Expansion Unit
Main Module