TH8320ZW1000 

5

69-2486—03

1H/1C Heat Pump (no auxiliary heat)

Rc 

Power [1]

[R+Rc joined by jumper]

O/B 

Changeover valve [5]

Compressor relay

Fan relay

24VAC common [3]

Optional THP9045 Wiring Module 
Terminal [9]

2H/1C Heat Pump (with auxiliary heat)

Equipment monitor [6, 7]

Emergency heat relay [8]

Aux 

Auxiliary heat relay (Heat 2) [8]

Rc 

Power [1]

[R+Rc joined by jumper]

O/B 

Changeover valve [5]

Compressor relay

Fan relay

24VAC common [3]

Optional THP9045 Wiring Module 
Terminal [9]

2H/2C Heat Pump (no auxiliary heat)

Y2 

Compressor 2 relay

Rc 

Power [1]

[R+Rc joined by jumper]

O/B 

Changeover valve [5]

Compressor 1 relay

Fan relay

24VAC common [3]

Optional THP9045 Wiring Module 
Terminal [9]

1H/1C System (2 transformers)

Rc 

Power (cooling transformer) [1, 2]

Power (heating transformer) [1, 2]

Heat relay

Compressor contactor

Fan relay

24VAC common [3, 4]

Optional THP9045 Wiring Module 
Terminal [9]

Heat Only System With Fan

Rc 

Power [1]

[R+Rc joined by jumper]

Heat relay

Fan relay

24VAC common [3]

Cool Only System

Rc 

Power [1]

[R+Rc joined by jumper]

Compressor contactor

Fan relay

24VAC common [3]

Optional THP9045 Wiring Module 
Terminal [9]

2H/2C System (2 transformers)

Y2 

Cool relay 2

W2 

Heat relay 2

Rc 

Power (cooling transformer) [1, 2]

Power (heating transformer) [1, 2]

Heat relay 1

Cool relay 1

Fan relay

24VAC common [3, 4]

Optional THP9045 Wiring Module 
Terminal [9]

Wiring guide—heat pump systems

Wiring

See [notes] below

  [1]  Power supply. Provide disconnect means and overload protection as required.
  [2]  Remove jumper for 2 transformer systems. 
  [3]  Connection to 24VAC common at the transformer is required.
  [4]  Common connection must come from cooling transformer. 
 [5] 

O/B

 set to control as either 

O

 or 

B

 in installer setup.

 [6] If 

L

 terminal is used, 24VAC common (terminal C) must be connected.

  [7]  Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor 

when set to Heat, Cool, or Off).

  [8]  Install field jumper between 

Aux

 and 

E

 terminals if there is no emergency heat relay.

  [9]  See "Optional THP9045 Wiring Module" on

 

page 14 for more details.

Содержание TH8320ZW1000

Страница 1: ...high efficiency furnaces heat pumps steam gravity Heat only including power to open and close zone valves Series 20 and normally open zone valves Heat only with fan Cool only 750 mV heating systems This manual covers the TH8320ZW1000 This thermostat contains a Lithium battery which may contain Perchlorate material Perchlorate Material special handling may apply See www dtsc ca gov hazardouswaste p...

Страница 2: ...tructions regarding recycling and proper disposal Grasp top and bottom of wallplate and pull to remove from thermostat CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before beginning installation Drill 3 16 holes for drywall Drill 7 32 holes for plaster Wall anchors Wire hole Mounting screws Must be installed by a trained experienced technician Read these...

Страница 3: ...ing during shipment and storage the thermostat is shipped with a plastic tab inserted in the battery holder This tab must be removed dur ing installation Simply pull the plastic tab out of the battery tray Make sure that the battery tray is fully inserted into the ther mostat Push excess wire back into the wall opening Plug wall opening with non flammable insulation Remove factory installed jumper...

Страница 4: ...ing system transformer C Common wire from secondary side of cooling system transformer Y 1st stage compressor contactor Y2 2nd stage compressor contactor Aux Auxiliary heat relay G Fan relay E Emergency heat relay L Heat pump reset powered continu ously when System is set to Em Heat system monitor when set to Heat Cool or Off O B Changeover valve for heat pumps K Optional THP9045 Wiring Module Ter...

Страница 5: ...r 1 R R Rc joined by jumper W Heat relay G Fan relay C 24VAC common 3 Cool Only System Rc Power 1 R R Rc joined by jumper Y Compressor contactor G Fan relay C 24VAC common 3 K Optional THP9045 Wiring Module Terminal 9 2H 2C System 2 transformers Y2 Cool relay 2 W2 Heat relay 2 Rc Power cooling transformer 1 2 R Power heating transformer 1 2 W Heat relay 1 Y Cool relay 1 G Fan relay C 24VAC common ...

Страница 6: ... thermostat with slots in wallplate then push gently until thermostat snaps into place Mount thermostat Set date and time Press st to set time Press st to set date Press st to set month Press st to set year Installer setup Press DONE to save changes Press DONE to save and exit 1 Press SYSTEM 2 Press and hold these two buttons until the display changes 3 Change settings as required see pages 7 9 M3...

Страница 7: ...nly 7 2 heat 1 cool heat pump with aux heat 8 2 heat 2 cool multistage conventional 9 2 heat 1 cool multistage conventional 10 1 heat 2 cool multistage conventional 11 2 heat 2 cool heat pump no aux heat 12 3 heat 2 cool heat pump with aux heat 0180 Fan control heating 0 Gas Oil heat equipment controls heating fan 1 Electric furnace thermostat controls heating fan 0190 Changeover valve O B termina...

Страница 8: ...ress requires 24VAC connection 0300 Manual Auto changeover 0 Manual changeover Heat Cool Off 1 Automatic changeover Heat Cool Auto Off 0310 Auto changeover deadband 3 Heat cool temperature 3 F apart 1 5 C Other options 2 9 2 F to 9 F 1 C to 5 C 0320 Temperature display 0 Fahrenheit 1 Celsius 0330 Daylight savings 1 Auto change to daylight savings time through 2007 and for areas that do not use the...

Страница 9: ... seconds after call for heat ends Other options 30 60 120 0660 Extended fan timer cool 0 Off 90 Fan runs for 90 seconds after call for cooling ends Other options 30 60 120 0670 Keypad lock 0 Keypad unlocked fully functional 1 Partially locked access to temperature settings only 2 Fully locked 0680 Heat temperature control 2 Standard temperature control recommended 1 Choose if room is warmer than s...

Страница 10: ...t and fan turn off 1 Heat turns on fan on if Function 0170 is set for heat pump or if Function 0180 is set to 1 2 Second stage heat turns on 4 Emergency heating system 0 Em Heat and fan turn off 1 Em Heat and fan turn on 2 Second stage heat turns on Auxiliary heat System test System status CAUTION EQUIPMENT DAMAGE HAZARD Compressor protection is bypassed during testing To prevent equipment damage ...

Страница 11: ...TH8320ZW1000 11 69 2486 03 F M32422 10 Wait 3 To remove the thermostat from the Z Wave network select 0 Z Wave enrollment F M32425 10 DONE 1 F M32424A 10 14 ...

Страница 12: ... this return route to access the distant node Enter leave power saving mode When requested from the Z Wave controller the thermostat adjusts its setpoint in order to decrease the power consumption of the HVAC equipment In addition using an Internet gateway enables the person to control the thermostat remotely through the Internet Fan Switch The thermostat can send the message containing the actual...

Страница 13: ...the actually supported system switch modes Thermostat Fan State The thermostat can send the message containing the actual state of fan based on fan state change The Fan state can be either Auto or On Thermostat Operating State The thermostat can send the message containing the actual state of the HVAC equipment based on equipment state change The thermostat provides the following operating states ...

Страница 14: ...re and the module is designed to receive the signal from the K terminal split that signal and reroute it to operate the compressor and or fan for normal operation See the THP9045 manual for further details Optional THP9045 Wiring Module Temperature Ranges Heat 40 to 90 F 4 5 to 32 C Cool 50 to 99 F 10 to 37 C Operating Ambient Temperature 0 to 120 F 18 to 48 9 C Shipping Temperature 30 to 150 F 34...

Страница 15: ...ll not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment ...

Страница 16: ... Trademark US Patent No 6 574 581 6 975 958 7 114 554 7 346 467 7 636 604 7 693 582 7 788 936 7 845 576 and other patents pending 2011 Honeywell International Inc 69 2486 03 M S Rev 05 11 Printed in U S A Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 Z Wave is a registered trademark of Zensys Inc and or its subsidiaries ...

Отзывы: