25
69-2028—01
Indoor Temperature High Limit Setting
The Indoor Temperature High Limit setting is used to
activate an alert when the displayed temperature on
the thermostat is higher than the value you set. The
setting range is 40° F (4° C) to 99° F (37° C) in 1°
increments. The factory default setting is 90° F
(32° C).
When a thermostat displays an indoor temperature
higher than your high limit setting and your dial-out
alert is active, the TAM dials out.
CAUTION
Property Loss Hazard.
Prepare to act promptly; time may be
critical.
Do not assume your designate received and
acted on the active alert.
CAUTION
Property Loss Hazard.
Do not rely only on the Telephone Access
Module to identify potential problems in
your home (like detecting high room
temperatures).
Have someone periodically check your home
while you are away.
If your indoor high limit setting is set to the factory
setting, you hear “
The high limit setting is 90° F
(32° C)
.”
If the indoor high limit setting is the value you want,
press the * key to return to the Main menu.
NOTE: The Indoor Temperature High limit setting
must be greater than the Low limit setting.
CHANGING THE INDOOR TEMPERATURE HIGH LIMIT
SETTING
1.
You hear “
To change the high limit setting,
press 1
.”
2.
Press 1.
• You hear “
Enter the high limit setting followed
by the # key
.”
3.
Enter a High Limit Setting from 40° F (4° C) to
99° F (37° C) in 1° increments and press the #
key.
• You hear “
Your high limit setting is (your high
limit setting)
.”
4.
If this is the high limit setting you want pro-
grammed, press the * key to return to the Main
menu.
If the indoor high limit setting is not entered correctly,
you hear “
Invalid setting
.” Follow the instructions
above to enter a new indoor high limit.