12
31-00400M-01 | Rev10-20
1 - ABOUT TC500A THERMOSTAT
Technical Specifications
Power Characteristics
Display
Operating Environment
Compliances
Table 1
Power Characteristics
Power Supply
Rated voltage: 24VAC 50/60Hz,
Working voltage range: 20-30VAC, UL listed class-2 transformer or
IEC 61558 listed transformer.
Power Consumption
(Display ON)
Max. 8.5VA @ 24VAC
(355mA @ 24VAC)
Min. Load
8VA (all BOs OFF)
Max. Load
96VA (all BOs ON)
Table 2
Display
Display Type
24 BPP TFT display with CTP
Resolutions
480x480 pixel
Active Display Area
4” diagonally
Backlight
LCD (Dimmable)
Table 3
Operating Environment
Ambient Operating
Temperature
32 to 122 °F (0 to +50°C)
Ambient Operating Humidity
10 to 90% relative humidity (non-condensing)
Storage Temperature
-40 to 150 °F(-40 to 65.5°C)
Protection Class
IP20
Table 4
Compliances
Certificates
CE, FCC, ICES, UL/cUL, RoHs, REACH, Title 24, BTL, ASHRAE, LEED, and Prop65.
Standards
EN 60730-1, EN 60730-2-9, EN 301489-1, EN 301489-17, EN 300328, EN
301893, EN 62479, UL60730-1, UL60730-2-9, Title 47 part 15 subpart B, Title 47
part 15 subpart C, RSS 210, ICES-003
Содержание TC500A
Страница 2: ......
Страница 8: ...8 31 00400M 01 Rev10 20 COMMERCIAL TOUCHSCREEN THERMOSTAT ...
Страница 16: ...16 31 00400M 01 Rev10 20 1 ABOUT TC500A THERMOSTAT ...